SvM Lec Power Flow Intro — Transcript

by Prof. Zack Subin · 4,738 words · 860 segments · language en · Watch on YouTube

Full transcript

  1. 0:02Hello everyone.
  2. 0:04This lecture is about power flow
  3. 0:06analysis.
  4. 0:07And in this first video, I'll give you a
  5. 0:10qualitative introduction to what it is
  6. 0:13we're trying to accomplish here.
  7. 0:15And then the next uh lecture will go
  8. 0:17into a bit more detail about the
  9. 0:20techniques uh that are used.
  10. 0:23So, in the big picture, what we're
  11. 0:26trying to do is we're trying to
  12. 0:28characterize
  13. 0:30an AC network,
  14. 0:33a synchronous uh AC network. This
  15. 0:35illustration
  16. 0:37uh is a simplified version of the
  17. 0:40Western Interconnect.
  18. 0:42And we're trying to identify the
  19. 0:45physical operating state of the network.
  20. 0:49And state is a term of art here. Uh the
  21. 0:52state variables
  22. 0:55are the voltages,
  23. 0:58where each voltage is a complex quantity
  24. 1:02or phasor with a magnitude and an angle.
  25. 1:06Um and the angle we might use
  26. 1:09uh lowercase delta or it could be theta
  27. 1:11as the variable
  28. 1:13that refers to the timing of the voltage
  29. 1:16waveform, right? Relative to the timing
  30. 1:20of the voltage
  31. 1:22somewhere else.
  32. 1:24Um and we're the the state of the the
  33. 1:28operating state of the system
  34. 1:31is defined by the set of voltages,
  35. 1:36magnitude and angle, everywhere at every
  36. 1:39node or bus of the network.
  37. 1:43And
  38. 1:44our job is to calculate
  39. 1:48those voltages, those state variables,
  40. 1:51based on the given input information,
  41. 1:54which is the power injection and
  42. 1:57withdrawal in terms of real power P and
  43. 2:00reactive power Q at each node
  44. 2:04or at each bus.
  45. 2:06And the power injection
  46. 2:09is much more along the lines of the way
  47. 2:11an economist thinks about the grid,
  48. 2:15right? Because that's how we capture our
  49. 2:17transactions.
  50. 2:19It's power being bought and sold into
  51. 2:21the grid.
  52. 2:23But physically
  53. 2:25we can't make power flow down a
  54. 2:29transmission line.
  55. 2:30The reason that power flows from
  56. 2:34node one to node two one end to the
  57. 2:37other of a transmission line is because
  58. 2:40there are different voltages maintained
  59. 2:42at either end.
  60. 2:44That's kind of the physical way uh to
  61. 2:47think about it. So, we are
  62. 2:50describing the physical state of the
  63. 2:53system as the set of voltages
  64. 2:56that are consistent with
  65. 2:59the power injections and withdrawals all
  66. 3:03across the grid.
  67. 3:05Um and as we'll see that's actually
  68. 3:08not a necessarily a unique one-to-one
  69. 3:11relationship.
  70. 3:13It this is its own topic because it's
  71. 3:15not a simple calculation
  72. 3:18um because it actually requires some
  73. 3:21trial and error or an iterative uh
  74. 3:24calculation
  75. 3:25and there's cases where it doesn't
  76. 3:27solve.
  77. 3:29Um
  78. 3:30so
  79. 3:32that's what I I want you to appreciate
  80. 3:35um the sort of subtlety and difficulty
  81. 3:37and really the profound takeaway here is
  82. 3:41that a physical way of of you know,
  83. 3:44thinking about power flow
  84. 3:46is very distinct from an economic way uh
  85. 3:49of thinking about power flow.
  86. 3:51This illustration is a vast
  87. 3:54oversimplification of the Western
  88. 3:56Interconnect. Um the real sort of
  89. 3:59professional grade representation has
  90. 4:02well over 10,000 nodes.
  91. 4:05Uh this is really distilled down to the
  92. 4:07major transmission paths and the major
  93. 4:10generation and load centers.
  94. 4:12Where the generators here are
  95. 4:13represented in circles.
  96. 4:15Uh the numbers are just
  97. 4:17cross-referenced. Uh they don't mean
  98. 4:19anything to us.
  99. 4:21Um and the arrows represent uh major
  100. 4:25load centers. So, you can appreciate the
  101. 4:27level of aggregation here, which is that
  102. 4:29in California we have, you know, the
  103. 4:31whole Bay Area is represented as a
  104. 4:33single load center.
  105. 4:35And then we have LA and so forth.
  106. 4:38Uh the big fat line here is our friend
  107. 4:41of Pacific DC Intertie.
  108. 4:44And uh you know, this is sort of a
  109. 4:48very simple representation, but just to
  110. 4:51give you sort of the mental picture
  111. 4:53of what
  112. 4:56um
  113. 4:57transmission operators um and uh
  114. 5:01authorities such as the California ISO
  115. 5:04would be looking at
  116. 5:06um and then they have computer
  117. 5:08algorithms running power flow analysis
  118. 5:12uh very frequently with updated values,
  119. 5:15where each analysis run is a snapshot of
  120. 5:19an in instantaneous operating state with
  121. 5:22some set of uh
  122. 5:25megawatt and megavar uh generation
  123. 5:29values across the system and some
  124. 5:31specific set of loads.
  125. 5:34And I want to distinguish that
  126. 5:36uh from optimal power flow, which we're
  127. 5:40not going to learn at all about how
  128. 5:42that's done, uh but you hear that
  129. 5:44terminology, and I want you to uh
  130. 5:47recognize the distinction here.
  131. 5:49The power flow analysis is answering a
  132. 5:52physics question. It's answering the
  133. 5:55physics question, what state
  134. 5:58of what or what set of state variables
  135. 6:02uh of voltage magnitudes and angles will
  136. 6:05produce the desired Ps and Qs
  137. 6:10all across the system.
  138. 6:12Optimal power flow
  139. 6:15answers the question
  140. 6:17based on some criteria or preferences
  141. 6:20that we define
  142. 6:21which dispatch, which combination of Ps
  143. 6:25and Qs at different locations do we like
  144. 6:28the best?
  145. 6:30And so to answer that question, it has
  146. 6:33to run many many power flow analyses
  147. 6:37with different scenarios that can then
  148. 6:40be compared according to the criteria
  149. 6:42such as least cost um and security
  150. 6:47constraints that uh will say a little
  151. 6:49bit more about later and so forth. But
  152. 6:51so optimal power flow is about finding a
  153. 6:54solution that we like the best that
  154. 6:57would give guidance uh to operations.
  155. 7:00Power flow analysis is what's running
  156. 7:02under the hood.
  157. 7:04And I want you to appreciate
  158. 7:07uh the complexity of power flow
  159. 7:10analysis, to appreciate the difference
  160. 7:14uh between thinking about power flow
  161. 7:17in a physical way rather than thinking
  162. 7:20about it in an economics way. And what
  163. 7:23we'll see is that
  164. 7:26you know, getting power to flow along a
  165. 7:29transmission link is not at all the same
  166. 7:33as sending a truckload of cargo from
  167. 7:35point A to point B
  168. 7:37because everything in the system
  169. 7:41is interactive
  170. 7:43to some degree.
  171. 7:45Uh but so power flow analysis would
  172. 7:48answer the type of question if if we
  173. 7:50make some change of power injection or
  174. 7:53power demand at some location I just
  175. 7:56arbitrarily picked some place
  176. 7:59what will be the effect on the way that
  177. 8:02power flows all across that network?
  178. 8:05Because any change at any one bus or
  179. 8:09node of this system
  180. 8:12any change in a voltage anywhere
  181. 8:15will result in a different set of state
  182. 8:20variables, a different maybe slightly
  183. 8:22different uh but different set of power
  184. 8:27flows, different set of currents through
  185. 8:30all these transmission lines. And so we
  186. 8:32might discover by running power flow
  187. 8:35analysis
  188. 8:36that if some market participants over
  189. 8:39here would like to
  190. 8:41change um their transaction power bought
  191. 8:44and sold somewhere
  192. 8:46that will have implications for the
  193. 8:49loading of a transmission line somewhere
  194. 8:51else in the system.
  195. 8:53And you don't know whether it does or
  196. 8:56not or whether that's consequential or
  197. 8:59not until you actually
  198. 9:02in effect simulate the whole system.
  199. 9:04You're in
  200. 9:05actually running the whole numbers to
  201. 9:08see again what set of voltages um
  202. 9:13will be consistent with that new uh
  203. 9:17desired state. And what I should say is
  204. 9:21that um we're starting with information
  205. 9:24about the transmission network which for
  206. 9:27purposes of this analysis we're holding
  207. 9:29fixed. There's no switches being thrown
  208. 9:32or anything.
  209. 9:33Um and once we know the voltages at
  210. 9:36every bus or every node and here all the
  211. 9:38buses are the horizontal lines in this
  212. 9:41uh toy illustration.
  213. 9:43Once we know all those voltages we
  214. 9:47already know all the uh impedances of
  215. 9:51all the transmission lines. So from that
  216. 9:53it's then straightforward to calculate
  217. 9:55the current
  218. 9:57uh in each line and the and the power
  219. 9:59flow in each line.
  220. 10:01But the hard part is getting from power
  221. 10:04injections to an entire profile of state
  222. 10:09variables, of voltage magnitudes and
  223. 10:11angles. And that's what the uh power
  224. 10:14flow
  225. 10:15analysis is doing.
  226. 10:18So,
  227. 10:20um this slide just summarizes exactly
  228. 10:22what I told you. We have um a set of
  229. 10:25impedances that could be expressed at in
  230. 10:27the inverse as admittances
  231. 10:30that uh represent
  232. 10:33all the properties of all the
  233. 10:35transmission lines and how they're
  234. 10:36interconnected.
  235. 10:38Um and in practice that's represented uh
  236. 10:41in a matrix format in linear algebra.
  237. 10:45And then we have a set of generation and
  238. 10:48loads that have some specified real and
  239. 10:51reactive power.
  240. 10:53Um the power flow analysis then cranks
  241. 10:57through the math to determine all the
  242. 10:59bus voltages and all the transmission
  243. 11:03link uh currents throughout the network.
  244. 11:06We are not looking at changes or
  245. 11:09transitions from one state into another.
  246. 11:11We're not looking at disturbances. This
  247. 11:14is strictly a steady state analysis.
  248. 11:17Um now one point I do want to make um
  249. 11:22and I won't get into too much detail
  250. 11:24here because you won't be doing
  251. 11:26this uh you won't be performing this uh
  252. 11:29calculation
  253. 11:31in detail, but I want you to appreciate
  254. 11:33that this is a non-linear
  255. 11:35um technique. And the a consequence of
  256. 11:39that is that there is not necessarily
  257. 11:43one solution.
  258. 11:45Uh it may be that there are multiple
  259. 11:48solutions that are consistent. Or it may
  260. 11:51be that there's no solution.
  261. 11:53And the set of power injections and
  262. 11:56demands that you specified would not
  263. 11:59actually work in physical practice.
  264. 12:05So, one way to describe non-linearity
  265. 12:08here
  266. 12:09is uh to just with this very simple uh
  267. 12:13toy example
  268. 12:15um to see that power and complex power
  269. 12:18would be letter S
  270. 12:20um for a branch here
  271. 12:25um
  272. 12:25in the middle. So, we're calling this uh
  273. 12:27current three
  274. 12:29um I three through this device, whatever
  275. 12:33it is,
  276. 12:34uh and voltage V3 across this device.
  277. 12:39This current branch will consume or
  278. 12:43produce some amount of complex power S
  279. 12:46which would be given by the product of
  280. 12:49current times voltage, right? Or using
  281. 12:51complex uh numbers, it's the complex
  282. 12:53conjugate of current uh times voltage, I
  283. 12:56star V.
  284. 12:58Um
  285. 12:59but because current and voltage are
  286. 13:02related to each other, it's really a
  287. 13:04quadratic function. So, we could say um
  288. 13:08it's really a function of voltage
  289. 13:10squared over the impedance
  290. 13:13uh or I squared times the impedance.
  291. 13:18Um
  292. 13:20It is It is not just a linear function
  293. 13:22because current and voltage are
  294. 13:25dependent on each other.
  295. 13:28It is
  296. 13:29the impedance of this branch that's sort
  297. 13:32of the the fixed quantity, but
  298. 13:34we're specifying the power, which is the
  299. 13:38product of current times voltage.
  300. 13:41So, it turns out in this case,
  301. 13:44there is uh if if we're given voltages
  302. 13:48V1 um
  303. 13:50and
  304. 13:52uh and V2 from two different sources and
  305. 13:56uh two currents are combining here,
  306. 13:59there are actually multiple ways to
  307. 14:01satisfy
  308. 14:03um
  309. 14:03some given amount of power that we want
  310. 14:06in this third branch.
  311. 14:09And it is that that is the non-linearity
  312. 14:13of the problem, so that this will force
  313. 14:16us to use a kind of trial and error
  314. 14:20uh method an iterative solution method
  315. 14:23to actually come up with um
  316. 14:25with the profile of voltages.
  317. 14:28Now, I'm going to expand
  318. 14:31this equation for complex power
  319. 14:35in uh a way that may look a little
  320. 14:37shocking.
  321. 14:39Um but these are the explicit power
  322. 14:44injections
  323. 14:45real power P and reactive power Q for
  324. 14:49each bus in the network or each node in
  325. 14:53the network uh where each bus has a
  326. 14:55subscript I.
  327. 14:57And here's
  328. 15:02what they are equal to. They are equal
  329. 15:05to the sum of power flows between node I
  330. 15:09and all the other nodes that node I
  331. 15:13whichever one were
  332. 15:15examining at the moment uh all the other
  333. 15:17nodes that it's connected to.
  334. 15:19So, how it's connected to the rest of
  335. 15:22the nodes in the network is expressed in
  336. 15:25terms of the G's and the B's which are
  337. 15:29the real and imaginary parts of the
  338. 15:31admittance.
  339. 15:33Admittance being the inverse of
  340. 15:34impedance. So, there's a conductance and
  341. 15:38a susceptance B um that being the
  342. 15:42imaginary part.
  343. 15:44And so, there may be some nodes some
  344. 15:48node pairs that aren't connected to each
  345. 15:50other. So, there's no conductance and
  346. 15:52susceptance between them. So, those
  347. 15:54terms don't show up, but summing over
  348. 15:58all the K nodes all the other nodes in
  349. 16:01the system
  350. 16:03um from one to uh to N and there should
  351. 16:08be an N on the top of the summation uh
  352. 16:10symbol here.
  353. 16:12Um
  354. 16:13we're going to add together all the
  355. 16:17power flows from node I to
  356. 16:22node K for all the Ks, which will be
  357. 16:25given by the product of the voltage
  358. 16:27magnitude. So, the um
  359. 16:29the absolute value signs uh represent
  360. 16:32the magnitude times the conductance and
  361. 16:35the cosine
  362. 16:37of the voltage phase angle difference
  363. 16:39between those nodes.
  364. 16:42And then another term that's related to
  365. 16:45the susceptance
  366. 16:47and the sign of that voltage phase angle
  367. 16:49difference between those nodes. And then
  368. 16:52I add that up for all the K nodes that
  369. 16:55my node I is connected to,
  370. 16:58and that will be equal to the power
  371. 17:00injection at node I.
  372. 17:03And an analogous equation for the
  373. 17:07reactive power injection and reactive
  374. 17:09power flows, except that sign uh and
  375. 17:13cosine are reversed and there's a
  376. 17:16a sign change.
  377. 17:18So, you will not have to worry about,
  378. 17:22you know, crunching through examples
  379. 17:25with this.
  380. 17:26The takeaway that I really want you to
  381. 17:29get uh from
  382. 17:32appreciating this uh these this pair of
  383. 17:35equations
  384. 17:37um is that if I give you the state
  385. 17:42variables, if I give you
  386. 17:45all the V sub I or V sub I V sub K,
  387. 17:50and I give you all the deltas,
  388. 17:53with that input information being armed
  389. 17:56with the knowledge of the transmission
  390. 17:58network, which is characterized by the
  391. 18:01Gs and the Bs for each branch connecting
  392. 18:05uh nodes,
  393. 18:08from that information, you could in a
  394. 18:11straightforward way uniquely calculate
  395. 18:14what are the Ps and Qs.
  396. 18:17Right? Because the Ps and the Qs are
  397. 18:19functions
  398. 18:20of
  399. 18:21the V's and the deltas.
  400. 18:24Where the G's and the B's are constants.
  401. 18:28But that's not what we're doing. We're
  402. 18:30going the other way around.
  403. 18:33We're given we're starting from the
  404. 18:36power injections and we're in a way
  405. 18:38trying to unpack or reverse engineer
  406. 18:41these equations
  407. 18:43to extract what is the physical with the
  408. 18:47set of physical state variables V and
  409. 18:50delta
  410. 18:51that would produce these P's and Q's.
  411. 18:54And so this is where uh it these
  412. 18:57functions are non-linear and we can't
  413. 19:00just
  414. 19:02turn them inside out. We can't just turn
  415. 19:05the signs and cosines uh inside out and
  416. 19:07solve. There's no closed-form solution.
  417. 19:11What we're going to have to do is a
  418. 19:12process of
  419. 19:15iterative computation that's essentially
  420. 19:17trial and error of plugging in different
  421. 19:20sets of V's and deltas to see if they
  422. 19:22give us the answer that we're looking
  423. 19:24for.
  424. 19:25Um
  425. 19:26now a qualitative takeaway
  426. 19:30again without really diving into the the
  427. 19:33details of how do you perform this
  428. 19:35calculation but a qualitative takeaway
  429. 19:38that is really worth remembering
  430. 19:41is that the real power
  431. 19:45injection and real power transfer
  432. 19:47between nodes
  433. 19:49will be more sensitive
  434. 19:52to the voltage phase angles delta. In
  435. 19:54other words, it'll be more sensitive to
  436. 19:56the timing of the voltage.
  437. 19:59And that is consistent with what we
  438. 20:01talked about in the context of
  439. 20:03generators.
  440. 20:05Uh consistent with this idea that if a
  441. 20:08generator is pushing harder
  442. 20:10and injecting more power into the system
  443. 20:14its rotor is going in the more forward
  444. 20:17position relative to other generators in
  445. 20:20the system.
  446. 20:21So that corresponds to a slight
  447. 20:24advancement in the timing of the voltage
  448. 20:27phase angle.
  449. 20:29So, that is one takeaway here is that
  450. 20:32the real power is going to be sensitive
  451. 20:35to the voltage phase angle delta or
  452. 20:38theta,
  453. 20:40however we call it.
  454. 20:42Whereas the reactive power Q is going to
  455. 20:45be more closely related to the voltage
  456. 20:48magnitude. And again, that is something
  457. 20:51that's consistent with our physical
  458. 20:53understanding of generator controls
  459. 20:55where the reactive power has to do with
  460. 20:59the excitation current and the generator
  461. 21:02bus voltage magnitude.
  462. 21:04Um and so
  463. 21:07it is
  464. 21:08to a first-order simplification,
  465. 21:11if we want to affect the generator bus
  466. 21:16voltage magnitude, we would change
  467. 21:20uh or adjust the real power. Excuse me.
  468. 21:24Stop. Rewind. If we want to change the
  469. 21:29generator bus voltage magnitude, we
  470. 21:31would adjust the reactive power output,
  471. 21:34and we would in practice do that with
  472. 21:35the excitation current in a synchronous
  473. 21:37machine.
  474. 21:39Um with an inverter, you do it
  475. 21:41digitally.
  476. 21:42Uh but it would the reactive power is
  477. 21:45what's related to the voltage magnitude
  478. 21:47primarily,
  479. 21:49and the real power is going to be
  480. 21:52related to the timing of the voltage.
  481. 21:55And with this delta, we're talking about
  482. 21:58angles, angle differences that are very
  483. 22:02subtle. Uh and in fact, on this
  484. 22:06just illustrative example with uh six
  485. 22:09buses,
  486. 22:10you can see just, you know, the types of
  487. 22:12angles we're talking about. It's just
  488. 22:14single-digit degrees. I mean, for a
  489. 22:16larger system, it could be tens of
  490. 22:18degrees.
  491. 22:20Um but it's a very subtle shift in the
  492. 22:23timing of that voltage sine wave. A
  493. 22:26little ahead means a lot more power
  494. 22:28injected, a little behind, a lot less
  495. 22:30power injected.
  496. 22:32So, um I kind of walked through this
  497. 22:35example in the book in uh chapter 12.
  498. 22:39Um
  499. 22:41these are just a again, and this is an
  500. 22:43example from Power World, which is a
  501. 22:45fabulous
  502. 22:47um
  503. 22:48teaching uh tool, and there's a free
  504. 22:51download version
  505. 22:53um that you could actually play with if
  506. 22:55you want to spend the time. You don't
  507. 22:57need to for this class.
  508. 22:59Um but um
  509. 23:02in this example, there are loads here
  510. 23:05with real and reactive specifications,
  511. 23:08generators with real and reactive
  512. 23:10specifications,
  513. 23:12and then each bus, or each of these
  514. 23:14heavy horizontal lines,
  515. 23:17um is characterized by a voltage
  516. 23:20magnitude, and that's specified here in
  517. 23:22per unit.
  518. 23:24Um so, it's independent of the actual
  519. 23:29um you know,
  520. 23:31nominal operating voltage of the system.
  521. 23:33It's in terms of whatever the nominal
  522. 23:36is. So, this one is 4% high, 1.04 per
  523. 23:40unit.
  524. 23:41Um so, if this whole system were
  525. 23:44operated nominally at 100 kilovolts,
  526. 23:47the voltage magnitude here would be 104
  527. 23:50kilovolt kilovolts per um
  528. 23:53uh root mean squared, and 2.77 degrees
  529. 23:58uh would be the angle, the positive
  530. 24:00angle, meaning it's ahead of time.
  531. 24:04Um and that's because this particular
  532. 24:07bus has more generation than load. So,
  533. 24:12intuitively, where there is a more
  534. 24:15positive
  535. 24:16voltage phase angle,
  536. 24:18that will tend to be associated with a
  537. 24:21more positive real power injection.
  538. 24:26Um and then we have real and reactive
  539. 24:29line flows. So, here the real ones are
  540. 24:31blue, the reactive ones are red.
  541. 24:34Um,
  542. 24:37the bus down here is more of a load bus,
  543. 24:39so that has a more negative voltage
  544. 24:42angle, a little behind.
  545. 24:45Um, and then there's this bus number one
  546. 24:48is a slack bus, and that has a
  547. 24:51significance.
  548. 24:52It's where we choose to uh
  549. 24:56define the time as being t equal to
  550. 24:58zero, where we press the button of the
  551. 25:00stopwatch, because voltage phase angle
  552. 25:04shifts need a reference. They need
  553. 25:07exactly one reference is where we draw
  554. 25:09the zero in our uh or how we choose a
  555. 25:13coordinate system when we're comparing
  556. 25:15multiple voltage phasors. So, we're just
  557. 25:17saying we're calling the voltage uh
  558. 25:20phase angle at this bus
  559. 25:22equal to zero,
  560. 25:24and that will also be the bus
  561. 25:27um that we um allow an adjustment
  562. 25:31um
  563. 25:32of power injection to make up for line
  564. 25:34losses. And
  565. 25:37why is that necessary? Because
  566. 25:41when we first specify power injections
  567. 25:44and demands,
  568. 25:45we don't know yet how those flows will
  569. 25:50um distribute themselves across the
  570. 25:52network.
  571. 25:54And until we know that, we can't know
  572. 25:56what the line losses are going to be.
  573. 25:59So, this is a simplified version that's
  574. 26:02not showing line losses, because what
  575. 26:04goes into a transmission line on one end
  576. 26:07equals what comes out at the other end.
  577. 26:10That's actually
  578. 26:12quite a simplification. So, if we go to
  579. 26:15the next level of detail, uh for each of
  580. 26:18these transmission lines here, which had
  581. 26:21been assigned some particular
  582. 26:24um
  583. 26:25real and imaginary impedance or
  584. 26:28admittance value,
  585. 26:30we can now calculate and the
  586. 26:33the power flow analysis will produce the
  587. 26:36values of the real and reactive line
  588. 26:39losses.
  589. 26:40Um where it's important to actually
  590. 26:44specify that the real line losses are
  591. 26:49a physical process of dissipating heat.
  592. 26:54That's the I squared R heating.
  593. 26:56And that is real money
  594. 26:59and real physical energy transfer.
  595. 27:02The reactive line losses are more of an
  596. 27:06accounting device.
  597. 27:09They can still be represented as I
  598. 27:12squared X.
  599. 27:14But as we've learned when we talked
  600. 27:17about reactive power,
  601. 27:19it's not really a quantity that's
  602. 27:21consumed or produced anywhere. So the
  603. 27:24term loss doesn't mean that physically
  604. 27:27something is getting lost. It means that
  605. 27:30this transmission line is acting as a
  606. 27:34predominantly inductive device.
  607. 27:37And so it is acting to quote consume
  608. 27:42reactive power
  609. 27:44in the context in which we've defined
  610. 27:46that where inductive things are
  611. 27:49consumers and capacitive things are
  612. 27:51producers of reactive power.
  613. 27:53And in fact, you can see that there's
  614. 27:56other transmission lines here that are
  615. 27:58capacitive in character.
  616. 28:01And they have
  617. 28:03negative reactive losses. In other
  618. 28:06words, they're generating VARs.
  619. 28:08Um
  620. 28:10and that will in practice that would be
  621. 28:12because they're lightly loaded
  622. 28:15um in this example. And in fact, it is
  623. 28:17it is because these are somewhat
  624. 28:20capacitive lines that the rules of thumb
  625. 28:24don't exactly
  626. 28:26work out across this whole um toy
  627. 28:30network, but it's worth um still
  628. 28:33remembering the general
  629. 28:37general rules of thumb that a more
  630. 28:39positive voltage phase angle will be
  631. 28:41associated with buses that produce more
  632. 28:44real power.
  633. 28:45A greater magnet voltage magnitude will
  634. 28:48be associated with buses that produce
  635. 28:51more reactive power.
  636. 28:53And conversely, if I have a big reactive
  637. 28:56load at some place in the network, that
  638. 28:59will tend to draw the voltage magnitude
  639. 29:01down a lot.
  640. 29:03Um and if I have a big real load, that
  641. 29:05will tend to pull the voltage phase
  642. 29:08angle behind or more negative at that
  643. 29:11location. Those are the general
  644. 29:14qualitative rules of thumb. And if you
  645. 29:17know just that much and you walk into a
  646. 29:21room with transmission operators,
  647. 29:23they'll respect you for knowing that
  648. 29:25much.
  649. 29:27Um
  650. 29:29Now, these rules are most apt for a
  651. 29:33network where the transmission lines
  652. 29:36are predominantly
  653. 29:38inductive.
  654. 29:39Um which, as we talked about with
  655. 29:42transmission line models, is usually the
  656. 29:45case um and is especially the case if if
  657. 29:49the transmission lines are more heavily
  658. 29:51loaded, their inductive properties will
  659. 29:54will dominate.
  660. 29:56Um
  661. 29:57And if transmission lines have uh a lot
  662. 29:59of resistance, that's more often the
  663. 30:02case for distribution actually than uh
  664. 30:04transmission lines.
  665. 30:06But, if they're behaving in a capacitive
  666. 30:08way, those rules don't work so well.
  667. 30:11Um
  668. 30:13So,
  669. 30:14with that, I want to come back to the
  670. 30:18optimal power flow.
  671. 30:20Uh so, now that you have a kind of a
  672. 30:23sense of what power flow analysis does,
  673. 30:26um
  674. 30:28we can have a little bit clearer
  675. 30:30distinction or to understand how So,
  676. 30:34power flow and individual power flow
  677. 30:36analysis run would be contributing
  678. 30:39to an optimal power flow analysis that
  679. 30:43runs many, many scenarios
  680. 30:46of of power flow.
  681. 30:48So, in OPF, we're trying to
  682. 30:51um
  683. 30:52optimize some quantity we've defined.
  684. 30:55So, maybe it's total generation cost and
  685. 30:58we want to find the minimum.
  686. 31:00Um but we also now want to take into
  687. 31:03account constraints as in what are we
  688. 31:07actually allowed to do in the real world
  689. 31:09or not.
  690. 31:11Um
  691. 31:12so, there are
  692. 31:15first of all, equality constraints,
  693. 31:17which are
  694. 31:19uh the real and reactive power balance.
  695. 31:22Um what goes in must come out including
  696. 31:25the losses.
  697. 31:27Um there are generator voltage set
  698. 31:29points, uh which is actually how in
  699. 31:32practice we're going to enforce
  700. 31:35uh the megavar injections that are
  701. 31:37necessary to keep the system uh
  702. 31:40balanced.
  703. 31:41And then there also as we uh learned in
  704. 31:44the previous uh set of lectures, um
  705. 31:47interchanges between areas, between
  706. 31:50neighboring areas,
  707. 31:52um that have to be accounted for.
  708. 31:56There are inequality constraints that
  709. 31:58basically say we have to keep certain
  710. 32:00quantities below some threshold, below
  711. 32:03some limit.
  712. 32:04So, we would have transmission line
  713. 32:06loading limits.
  714. 32:08Um they could be thermal limits or they
  715. 32:11could be stability limits of some sort.
  716. 32:15Um but
  717. 32:16uh
  718. 32:17there would be some applicable
  719. 32:19constraints that if we come up with some
  720. 32:22scenario of megawatts injected here and
  721. 32:24consumed there,
  722. 32:26and we run the power flow analysis and
  723. 32:28the power flow says, "Oh, you're going
  724. 32:30to have such and such a current through
  725. 32:32here or number of megawatts flowing
  726. 32:34through here."
  727. 32:36If that crosses a line, if that exceeds
  728. 32:40a threshold that in our engineering
  729. 32:43analysis we've decided that's some safe
  730. 32:47limit,
  731. 32:49then we have to go back and say,
  732. 32:52"Sorry, you're not allowed to make that
  733. 32:55transaction. We can't authorize that
  734. 32:59transaction if injecting so many
  735. 33:01megawatts here and selling them down
  736. 33:04there because that would violate a
  737. 33:08transmission
  738. 33:11loading limit.
  739. 33:13Um so, there are limits on all kinds of
  740. 33:17equipments, right? Limits on
  741. 33:18transformers that we talked about. Those
  742. 33:21would be mostly thermal limits.
  743. 33:23Uh there could be uh flow limits at the
  744. 33:25interface at the borders between uh
  745. 33:28jurisdictions.
  746. 33:29And especially for long transmission
  747. 33:31lines, there could be different physical
  748. 33:33factors
  749. 33:35uh
  750. 33:36that would say, you know, you cannot
  751. 33:38transfer more than a certain amount of
  752. 33:42power, more than some number of
  753. 33:44megawatts on this link.
  754. 33:46Sometimes those transmission line limits
  755. 33:49uh could be articulated in terms of an
  756. 33:51angle difference. That would be a
  757. 33:52stability limit.
  758. 33:55Where, you know, if the power flow
  759. 33:57solution comes out with, you know, your
  760. 34:00delta one voltage angle is one number
  761. 34:02here and so many degrees different um on
  762. 34:06the other side of this transmission
  763. 34:08line,
  764. 34:09that may be exceeding some stability
  765. 34:12limit. And so then you have to go back
  766. 34:13and say,
  767. 34:15"That set of power injections is not
  768. 34:18allowed."
  769. 34:19And let's make adjustments to uh the
  770. 34:23dispatch or uh the the way that the
  771. 34:27market was supposed to clear because
  772. 34:30this arrangement violates our
  773. 34:32constraints, so we have to pull the
  774. 34:34generation from somewhere else.
  775. 34:37Um
  776. 34:38the generators obviously have physical
  777. 34:41limits of what they can produce. They
  778. 34:43will have limits of how much reactive
  779. 34:45power they can
  780. 34:47um
  781. 34:48inject. And then there are
  782. 34:51um limits on the bus voltage magnitudes
  783. 34:54that are acceptable. So perhaps I want
  784. 34:56to keep all of the bus voltages with
  785. 34:59within plus or minus 5% of nominal.
  786. 35:03So now you get the picture
  787. 35:06of how we want to have some dispatch
  788. 35:10of megawatts and megavars from
  789. 35:14thousands of generators across the
  790. 35:16system
  791. 35:17to meet the load across the system.
  792. 35:21But to check whether that's feasible and
  793. 35:24okay with the transmission network,
  794. 35:28we have to run power flow analysis.
  795. 35:31We have to check that it meets all of
  796. 35:35the constraints. It doesn't violate
  797. 35:38anything.
  798. 35:40And then if we say, "All right, that
  799. 35:43works well."
  800. 35:45We might run another scenario and say,
  801. 35:48"Okay, well let me tweak the generation
  802. 35:50values some because maybe there are some
  803. 35:53contracts that are not up for
  804. 35:55negotiation, but there's some generators
  805. 35:58that as a system operator I can dispatch
  806. 36:01and let's see if I can come to another
  807. 36:04dispatch arrangement that would be uh
  808. 36:08less costly but still not violate any of
  809. 36:11these constraints."
  810. 36:13And so then I would iterate and run many
  811. 36:16many power flow calculations until I
  812. 36:19come up with the one that's aha, optimal
  813. 36:22according to my criteria.
  814. 36:25Um
  815. 36:26in orange here is a side comment uh
  816. 36:29which is that n minus one security
  817. 36:31analysis
  818. 36:33is an an important piece of these
  819. 36:36constraints. And that will be a separate
  820. 36:40um piece of a lecture,
  821. 36:43but um just in a nutshell, n minus one
  822. 36:46means one piece breaks.
  823. 36:50And the whole thing shouldn't the whole
  824. 36:53grid shouldn't fall apart. No customers
  825. 36:55should be out of power.
  826. 36:57Anyone generator, anyone transmission
  827. 37:00link
  828. 37:01could get struck by lightning or
  829. 37:04suddenly be taken out of commission for
  830. 37:06reasons we don't know.
  831. 37:08And
  832. 37:10the overall dispatch or power flow
  833. 37:12scenario that we choose should be robust
  834. 37:15with respect to any one of those
  835. 37:17contingencies happening.
  836. 37:20Um n minus two would be that well, two
  837. 37:23things could go wrong and we'd still be
  838. 37:25fine. So, all of these inequalities
  839. 37:28would still have to be satisfied
  840. 37:31even if we lose any one and typically we
  841. 37:36want to
  842. 37:38say well, what's the worst that could
  843. 37:39happen? What if the biggest generator
  844. 37:42right in the middle goes out or the
  845. 37:45biggest transmission link goes out?
  846. 37:47Um
  847. 37:48and in fact, choosing the contingencies
  848. 37:53for a contingency analysis is
  849. 37:57is a whole settled business and mistakes
  850. 37:59have been made.
  851. 38:01Where something gets overlooked that
  852. 38:03seems like oh, this would be a small
  853. 38:05failure, but it's actually
  854. 38:06consequential.
  855. 38:08And again, that's because the power flow
  856. 38:09problem is so
  857. 38:11counterintuitive.
  858. 38:14Um so, I will pause here and the next
  859. 38:18lecture will go a little bit more into
  860. 38:19the math.

About this transcript

This page contains the full transcript of SvM Lec Power Flow Intro by Prof. Zack Subin, generated from the public captions YouTube serves with the video. The transcript has 4,738 words across 860 segments, with the original timestamps preserved so you can click any line to jump to that moment in the embedded player.

What you can do with it

Use the transcript to take notes, quote the speaker, build a study guide, generate a summary with ChatGPT or Claude via the YouTube Summary tool, or export it as a timed subtitle file with YouTube to SRT. You can also re-open it in the transcriber to choose a caption track available on the video.

Free YouTube transcript tool

YouTube2Text is a free YouTube transcript generator — no signup, no daily limit. Paste any YouTube link and get the full transcript instantly, with timestamps, click-to-jump, caption language selection, AI prompts for ChatGPT, Claude, and Gemini, and exports to TXT, SRT, VTT, or Markdown.