YouTube2Text

Power Factor Explained - The basics what is power factor pf — Transcript

by The Engineering Mindset · 1,979 words · 289 segments · language en · Watch on YouTube

Full transcript

  1. 0:04Hey there guys.
  2. 0:05Paul here from TheEngineeringMindset.com
  3. 0:07In this video, we're going to be discussing
  4. 0:09power factor, we're going to start off really
  5. 0:12easily with some simple analogies
  6. 0:13to help you understand the basics, and then
  7. 0:15we'll advance it into electrical
  8. 0:17engineering terms with some work examples
  9. 0:19as well as looking at what is power factor,
  10. 0:21what is a good and bad power factor,
  11. 0:24what causes bad power factor,
  12. 0:26and how to fix bad power factor.
  13. 0:28So what is power factor?
  14. 0:30Power factor is a unitless number
  15. 0:32using alternating current circuits.
  16. 0:34It can be used to refer to a single piece of
  17. 0:36equipment such as an induction motor or through
  18. 0:39electricity consumption of an entire building.
  19. 0:42In either case, it represents the ratio between
  20. 0:44true power and apparent power.
  21. 0:46The formula being PF equals KW divided by kVa.
  22. 0:50So what does that mean?
  23. 0:52My favourite analogy to explain this
  24. 0:54is to use the beer analogy.
  25. 0:56We pay for beer by the glass, but inside the glass
  26. 0:59there is both beer and foam.
  27. 1:01The more beer we have, the less foam there will be, so
  28. 1:03we get very good value for money.
  29. 1:05If there is a lot of foam, then there's not a lot of beer,
  30. 1:08and so we're not getting very good value for money.
  31. 1:10The beer represents our true power or kW, our kilowatts.
  32. 1:14This is the useful stuff you want and need.
  33. 1:16This is what does the work.
  34. 1:18The foam represents our reactive power, or our
  35. 1:20kVar, Kilovolt-Amps Reactives.
  36. 1:24This is the useless stuff, there will always
  37. 1:26be some, we have to pay for it, we can't use it
  38. 1:28so we don't really want much of it.
  39. 1:30It does actually have a use and a purpose,
  40. 1:33but we'll see why later in the video.
  41. 1:35The combination of these kW are kilowatts
  42. 1:38and the kVar are Kilovolts-Amp Reactive,
  43. 1:41is our apparent power or our kVA, meaning
  44. 1:44the kilovolt amps.
  45. 1:45Power factor is therefore
  46. 1:46the ratio of useful power or true power
  47. 1:50in kilowatts, or kW divided by what we're
  48. 1:52charged for in kVA, kilovolt-amps.
  49. 1:55So it's telling us how much value for money
  50. 1:58we're getting for the power we consume.
  51. 2:00If we briefly touch on electrical engineering,
  52. 2:03and I will keep this part brief, then we might
  53. 2:05see this express as a power triangle.
  54. 2:07In this case I'll draw it as leading
  55. 2:09power factor as it's easier to visualize.
  56. 2:12The beer or true power is the adjacent line.
  57. 2:15Then we have the foam which is the reactive
  58. 2:16power on the opposite.
  59. 2:18Then for the hypotenuse side, which is the
  60. 2:20longest side, we have the apparent power.
  61. 2:23This is at an angle from the true power, the
  62. 2:25angle is known as theta.
  63. 2:26You see as the reactive power or the foam
  64. 2:29increases then so does the apparent power
  65. 2:31of the kVA.
  66. 2:33WE could then use trigonometry
  67. 2:34to calculate this triangle.
  68. 2:35I won't in this video as I'm just covering the basics,
  69. 2:38so we'll just see the formulas you need,
  70. 2:40but we'll do some calculations
  71. 2:41and worked examples later in this video.
  72. 2:44If we look at a typical residential
  73. 2:46electricity bill, then we'll typically see
  74. 2:48just a fee for the amount of kilowatts
  75. 2:49hours used, because the power factor
  76. 2:51and the electricity consumption will
  77. 2:53be very low.
  78. 2:54So the electricity companies
  79. 2:55tend to not worry about this.
  80. 2:57However on commercial and industrial electricity invoices,
  81. 3:00especially buildings with smart
  82. 3:02or interval electricity meters, then we'll
  83. 3:04likely see charges and information
  84. 3:06for the amount of kilowatts, kilowatt hours,
  85. 3:08kilovolt amps, and kilovolts-amps reactive used.
  86. 3:11Large buildings in particular will often
  87. 3:13see reactive power charges in there.
  88. 3:15But this depends on the electricity supplier,
  89. 3:17and the agreement they have with the consumer.
  90. 3:19They reason they charge a penalty for this
  91. 3:21is because when large consumers have bad
  92. 3:23power factors, they're increasing
  93. 3:25the current flow through
  94. 3:26the electricity network, and causing voltage drops,
  95. 3:29which reduces the supplier's distribution
  96. 3:31capacity and has a knock on effect
  97. 3:34for the other customers.
  98. 3:35Cable are rated to handle
  99. 3:38a certain amount of current flowing for them.
  100. 3:39So if a lot of large consumers connect
  101. 3:41with bad power factor, then the cables could overload.
  102. 3:45It could also struggle
  103. 3:46to meet the demands and the capacity agreements,
  104. 3:48and then no new customers will be able
  105. 3:49to connect, until they either replace the cables,
  106. 3:52or install additional cables.
  107. 3:54Reactive power charges occur when the
  108. 3:56power factor of a building falls below
  109. 3:58a certain level.
  110. 3:59This level is defined by
  111. 4:01the electricity supplier, but it typically
  112. 4:03starts around 0.95 and below.
  113. 4:06A perfect power factor would be one, however
  114. 4:08in reality, this is almost impossible to achieve.
  115. 4:11We'll come back to this part
  116. 4:12later in the video.
  117. 4:14In large commercial buildings, the overall
  118. 4:16power factor is likely to sit
  119. 4:18in the following categories.
  120. 4:19Good power factor is generally between one and 0.95
  121. 4:24Poor power factor is anything from 0.95 and 0.85.
  122. 4:28Bad power factor is anything below 0.85.
  123. 4:32Commercial office buildings are usually somewhere
  124. 4:34between 0.98 and 0.92.
  125. 4:37Industrial buildings could be as low as 0.7.
  126. 4:40We'll look out what causes this shortly.
  127. 4:43Let's first have a look at an example.
  128. 4:46If we compare two induction motors, that
  129. 4:49both have an output of 10 kilowatts, and are
  130. 4:51connected to a three phase 415/50 hertz supplier,
  131. 4:54one has a power factor of 0.87, and the other
  132. 4:58with the power factor of 0.92.
  133. 5:00Both motors will deliver 10 kilowatts of work,
  134. 5:03but the first motor has a lower power factor
  135. 5:05compared to the second one.
  136. 5:07Meaning we're not getting as much value for money.
  137. 5:10The first motor will need to draw
  138. 5:1111.5 kVA from the electricity grid to provide
  139. 5:15the 10 kilowatts of power, the second motor
  140. 5:18will need to draw just 10.9 kVA from
  141. 5:20the electricity grid to provide
  142. 5:22the same 10 kilowatts of power.
  143. 5:23This means the first motor has 5.7kVAr
  144. 5:27and the second motor has just 4.3kVArs
  145. 5:30Remember our kilowatts is the beer,
  146. 5:32and that's the useful stuff.
  147. 5:33The kVArs are the foam, that's the not so useful stuff.
  148. 5:36The kVA is what we're going to pay for,
  149. 5:39and that's the kilowatts and the kVAr combined.
  150. 5:42How did I calculate that?
  151. 5:43For kVA I use kilowatts divided by power factor
  152. 5:46so 10 divided by 0.87 to get 11.5 kVa.
  153. 5:51For kVAr I use the square root of kVA squared,
  154. 5:54subtract kilowatts squared.
  155. 5:56So the square root
  156. 5:57of 11.5 kVA squared minus 10 kilowatts squared.
  157. 6:00We could've also found the power factor
  158. 6:02from the kilowatt and the kVA, using
  159. 6:0410 kilowatt divided by 11.5 kVA.
  160. 6:07We could've found the kilowatts from
  161. 6:09the power factor and the kVA using 0.87
  162. 6:12divided by 11.5 kVA to get 10.
  163. 6:16So what causes poor power factor?
  164. 6:18In most cases the power factor
  165. 6:20is affected by inductive loads.
  166. 6:23If we have a purely resistive load, such as
  167. 6:25an electrical resistive heater, then the voltage
  168. 6:27and the current wave forms would be in sync
  169. 6:29or very close.
  170. 6:31They would both pass through their maximum
  171. 6:33and minimum point and then pass through
  172. 6:35the zero axis at the same time.
  173. 6:37The power factor in this case is one,
  174. 6:39which is perfect.
  175. 6:41If we drew a phaser diagram, then the voltage and
  176. 6:43and current would be parallel.
  177. 6:45So all the energy drawn from the electricity
  178. 6:47supply goes into doing work.
  179. 6:50In this case creating heat.
  180. 6:53But if we took an inductive load, such as
  181. 6:55an induction motor, then the coils
  182. 6:57magnetic field holds back the current and results
  183. 7:00in the phase shift where the voltage
  184. 7:01and the current waveforms fall out of sync
  185. 7:04with each other, so the current passes
  186. 7:06through the zero point after the voltage.
  187. 7:09This is referred to as a lagging power factor.
  188. 7:12Earlier in the video,
  189. 7:13I said the foam or the kVAr is useless.
  190. 7:16That's not exactly true.
  191. 7:18You actually need some reactive power to create
  192. 7:20and maintain the magnetic field
  193. 7:22which rotates the motor.
  194. 7:24The reactive power is wasted in the sense
  195. 7:26that we get no work from it.
  196. 7:27But we still have to pay for it although we do need it
  197. 7:30to be able to do the work in the first place.
  198. 7:33If we drew a phaser diagram for a purely
  199. 7:35inductive load, then the current would be at an
  200. 7:37angle below the voltage line.
  201. 7:39Meaning not all the electricity consumed is doing work.
  202. 7:43If we took a purely capacitive load,
  203. 7:45then the opposite happens
  204. 7:46to the inductive load.
  205. 7:48The voltage and current are out of phase, except
  206. 7:50this time the voltage is held back.
  207. 7:53This causes leading power factor.
  208. 7:55Again this will mean that not all of the
  209. 7:57electricity being used is being used to do work.
  210. 8:00But we still have to pay for it regardless.
  211. 8:03If we drew a phaser diagram for a
  212. 8:04purely capacitive load, then the current line
  213. 8:07will be at an angle above the voltage line,
  214. 8:09as it's leading.
  215. 8:12Correcting poor power factor.
  216. 8:14What can we do to correct poor power factor
  217. 8:17and reactive power charges?
  218. 8:19In most case we come across lagging power factor
  219. 8:21caused by inductive loads.
  220. 8:23To correct poor power
  221. 8:24factor, we can add capacitors or inductors to
  222. 8:27the circuit, which will realign the current back
  223. 8:29into phase and bring the power factor
  224. 8:31closer to one.
  225. 8:32If we have a lagging power factor, caused by
  226. 8:34high inductive loads in the circuit,
  227. 8:36then we add capacitors.
  228. 8:38If we have a leading power
  229. 8:39factor, caused by high capacitive loads, then we
  230. 8:42add an inductive load to the circuit.
  231. 8:44These need to be calculated, and we'll see
  232. 8:46some example calculations of this
  233. 8:47at the end of the video.
  234. 8:49So why should we fix poor power factor?
  235. 8:51Poor power factor means you need to draw more
  236. 8:53power from the electricity network
  237. 8:55to do the same amount of work, therefore
  238. 8:57the cables need to be larger so the installation
  239. 9:00is going to cost more money.
  240. 9:01If the power factor becomes too low,
  241. 9:03then the electricity supplier might charge you
  242. 9:05a penalty fee or reactive power charge.
  243. 9:08Poor power factor can cause losses
  244. 9:10in the equipment, like transformers,
  245. 9:11and leads to high heat gains.
  246. 9:13It can lead to voltage drops and can even reduce
  247. 9:15the life expectancy of equipment
  248. 9:17in extreme scenarios.
  249. 9:19Capacitor calculations for power factor correction.
  250. 9:23Let's look at a simplified example of calculating
  251. 9:26the size of a capacitor to improve
  252. 9:27the power factor of a load.
  253. 9:30The building has a three phase power supply
  254. 9:32and has a total load of 50 kilowatts of work.
  255. 9:35It also has a power factor of 0.78, but we
  256. 9:38want it to be 0.96 to avoid penalty charges.
  257. 9:42Currently the building has a total apparent power
  258. 9:44or kVA value of 64.1 kVA and we find that
  259. 9:49by just dividing the kilowatts, 50 kilowatts
  260. 9:52by the power factor of 0.78.
  261. 9:54It also has a reactive power of 40.1 kVAr.
  262. 9:58We find that by taking the square root of the
  263. 10:00kVA squared and subtracting it from
  264. 10:03the kilowatts squared.
  265. 10:04So take the squared root
  266. 10:06of 64.1 squared minus 50 kilowatts squared.
  267. 10:09Then we calculate what the value should be
  268. 10:11if we had a power factor of 0.96.
  269. 10:14SO our apparent power should be 52.1 kVA.
  270. 10:18We find that from 50 kilowatts divided by
  271. 10:210.96 power factor.
  272. 10:23Then we find our reactive power which is
  273. 10:25the square root of the kVA squared
  274. 10:27minus the kilowatts squared.
  275. 10:29So the square root
  276. 10:30of 52.1 kVA squared minus 50 kilowatts squared
  277. 10:34which gives us 14.6 kVAr.
  278. 10:37The capacitor therefore
  279. 10:38needs to make up the difference between these.
  280. 10:40So 40.1 kVAr minus 14.6 kVAr which equals
  281. 10:45a 25.5 kVAr capacitor.
  282. 10:48Okay guys, that's it for this video,
  283. 10:50but if you want to continue your learning,
  284. 10:52check out these videos here.
  285. 10:53I'll catch you there for the next lesson.
  286. 10:55Leave you questions in
  287. 10:56the comments section down below, and don't forget
  288. 10:57to follow us on Facebook, Instagram, Twitter,
  289. 11:00as well as TheEngineeringmindset.com.

About this transcript

This page contains the full transcript of Power Factor Explained - The basics what is power factor pf by The Engineering Mindset, generated from the public captions YouTube serves with the video. The transcript has 1,979 words across 289 segments, with the original timestamps preserved so you can click any line to jump to that moment in the embedded player.

What you can do with it

Use the transcript to take notes, quote the speaker, build a study guide, generate a summary with ChatGPT or Claude via the YouTube Summary tool, or export it as a timed subtitle file with YouTube to SRT. You can also re-open it in the transcriber to translate the transcript into 100+ languages.

Free YouTube transcript tool

YouTube2Text is a free YouTube transcript generator — no signup, no daily limit. Paste any YouTube link and get the full transcript instantly, with timestamps, click-to-jump, translation to 100+ languages, AI prompts for ChatGPT, Claude, and Gemini, and exports to TXT, SRT, VTT, or Markdown.