  1. 0:02hi and welcome to this
  2. 0:04video on installation coordination the
  3. 0:07lightning part
  4. 0:11so in this video we are going to
  5. 0:14see how to perform an insulation
  6. 0:16coordination
  7. 0:17in emtp and especially
  8. 0:20and focus of course on the lightning
  9. 0:25so before watching this video i highly
  10. 0:28recommend you to take a look
  11. 0:29at the other recorded video which is
  12. 0:31called
  13. 0:32origin and classification of
  14. 0:34overvoltages
  15. 0:36i will do some reminders
  16. 0:39here but to fully understand the content
  17. 0:42of this video it's
  18. 0:43highly recommended to watch this this
  19. 0:45first one
  20. 0:47okay so well first of all if you uh
  21. 0:51the first reminder actually from this
  22. 0:52video it's about
  23. 0:54the different type of overvoltages there
  24. 0:57are like
  25. 0:59very fast transients over voltages which
  26. 1:03are actually the fastest then you have
  27. 1:05the fast front over voltage
  28. 1:07which are lightning over voltages you
  29. 1:09have switching
  30. 1:10over voltages and temporary overvoltages
  31. 1:14which are
  32. 1:15the slowest like typically a fundamental
  33. 1:18frequency over voltage like a single
  34. 1:20phase ground fault or
  35. 1:22load rejection for resonance
  36. 1:25why it is important again to repeat what
  37. 1:28is important to
  38. 1:30classify those over voltages it's
  39. 1:32because
  40. 1:33an apparatus will
  41. 1:36waste them a certain level according to
  42. 1:40the shape of your voltage
  43. 1:43for lightning or voltage the
  44. 1:46the surge is very steep and so you will
  45. 1:49have
  46. 1:49here the time from zero to peak which is
  47. 1:52very short
  48. 1:53in this condition the apparatus will
  49. 1:56withstand
  50. 1:57and higher over voltage compared to
  51. 2:01a switching over voltage where the time
  52. 2:03to peak is much
  53. 2:04slower and so it means that the maximum
  54. 2:07level
  55. 2:08which for lightning is called a bil
  56. 2:11basic impulse level the
  57. 2:15this level is higher than for a
  58. 2:18switching level
  59. 2:21okay so here you can see approximately
  60. 2:23the dynamic of this
  61. 2:24search for lightning the classification
  62. 2:28so basically when we are going to do a
  63. 2:30an analysis
  64. 2:32we do a simulation or even if you have
  65. 2:35something
  66. 2:36a real lightning strike on field
  67. 2:39we kind of assume that the shape of the
  68. 2:42overvoltage
  69. 2:43we will have will be close enough
  70. 2:47to the lab test all equipment
  71. 2:50are doing all the tests
  72. 2:53and equipment have passed through and so
  73. 2:56that the level
  74. 2:57uh the bil which was obtained by lab
  75. 3:00measurements
  76. 3:01to determine the bil we assume that
  77. 3:04for the any shape of lightning strike we
  78. 3:07will get
  79. 3:08during the simulation or on field will
  80. 3:10be similar and so the same level
  81. 3:12can be assumed
  82. 3:17okay so uh there are several type of
  83. 3:21lightning over voltages uh first of all
  84. 3:23you have the induced overvoltage
  85. 3:25and this is mostly uh this mostly
  86. 3:28affects
  87. 3:29the distribution network it's when the
  88. 3:30lightning strike does not strike
  89. 3:32directly the line but something close by
  90. 3:35and you have an overvoltage on the line
  91. 3:39for that there are some tools actually
  92. 3:40we have one here which is called earlier
  93. 3:43liov which is used in this purpose but
  94. 3:47that's not what we're going to do today
  95. 3:50then you have what is called
  96. 3:53the lightning strike so when the
  97. 3:56lightning strike
  98. 3:57on a shield wire so you have the tower
  99. 4:00and at the top you have two ground wire
  100. 4:01which are called a chill wire
  101. 4:03those are designed to capture lightning
  102. 4:07and so you may have over voltages when
  103. 4:09the voltage rises
  104. 4:10so high on those chill wire that you
  105. 4:13have
  106. 4:14a flash over between the ground and the
  107. 4:17face
  108. 4:17and because it is because between the
  109. 4:19ground and the face it's called a back
  110. 4:21flashover
  111. 4:22and so that's typically what we study
  112. 4:24when we do empty simulation mtp
  113. 4:27simulations or
  114. 4:28we study this case the backlash we also
  115. 4:31will apply
  116. 4:31a lightning strike on the tower top
  117. 4:34on the chill wire
  118. 4:38in some region of the world where the
  119. 4:42the lightning density isn't so high
  120. 4:45um it's not economic it doesn't make
  121. 4:47sense economically to
  122. 4:49put those shielding wires or to
  123. 4:52perfectly protect a line very often you
  124. 4:54will need two chilling wires
  125. 4:56so often you will put only one or none
  126. 4:58according to
  127. 5:00again some economical uh consideration
  128. 5:04and if you don't have so many lightnings
  129. 5:06on the region and so in this case it may
  130. 5:08happen that the lightning strikes
  131. 5:10straight on a phase without striking
  132. 5:14the shielding this is cause this is
  133. 5:16called a direct strike or
  134. 5:18shielding failure so this is also
  135. 5:20something you have to study in emtp and
  136. 5:22make sure
  137. 5:23the overvoltage
  138. 5:26there is no too bad of a voltage for
  139. 5:28that
  140. 5:30typically we don't study lightning
  141. 5:33tracking inside the substation
  142. 5:35because we assume that the substation is
  143. 5:37protected and you have lightning mass
  144. 5:38which will capture the lightning
  145. 5:40and so the electrical operators are
  146. 5:43safe inside the substation so when you
  147. 5:46do the emtp simulation
  148. 5:47you have a device which is a lightning
  149. 5:50strike which we will see later in the
  150. 5:52video which is a current source
  151. 5:53you will connect this current source on
  152. 5:56the incoming transmission lines but not
  153. 5:58inside the substation
  154. 6:02so the objective of any mtp study here
  155. 6:06there will be several things if you talk
  156. 6:08about transmission line itself
  157. 6:10you will come out with what is called
  158. 6:11the line performance
  159. 6:13which is the flash over rate of an
  160. 6:16overhead line
  161. 6:17okay you have a transmission line how
  162. 6:19often
  163. 6:20you will have a back flashover or
  164. 6:23shielding failure
  165. 6:26and so this is typically like a number
  166. 6:28ones per
  167. 6:29100 year 200 years and so on
  168. 6:32it can be much less or much more so this
  169. 6:35is for transmission lines
  170. 6:37and then if you talk about equipment
  171. 6:40inside substations now we are going to
  172. 6:42determine the rate of failure
  173. 6:46if you have so the first step will be
  174. 6:47you will have a back flash over on the
  175. 6:49line
  176. 6:49and then this back flashover will create
  177. 6:51an overvoltage on
  178. 6:53phases which will propagate to the
  179. 6:55substation and may damage
  180. 6:57equipment okay so there we will see in
  181. 7:00this
  182. 7:01video the procedure to determine that
  183. 7:04and finally it's also to determine uh
  184. 7:06the survivor ratings
  185. 7:08um so the switching the lightning
  186. 7:14surge
  187. 7:16the impulse level of the the third
  188. 7:19arrestor but also the position of the
  189. 7:21sort arrester
  190. 7:22and this is crucial for lightning um
  191. 7:26one thing you have to remember which is
  192. 7:28important is that for lightning
  193. 7:30the substation is actually a circuit and
  194. 7:32you don't assume that the voltage is the
  195. 7:34same at each point in the substation
  196. 7:36which means that if you have a
  197. 7:38substation connected to a transformer
  198. 7:39but there is a conductor in between
  199. 7:41during a lightning strike the voltage at
  200. 7:45the
  201. 7:45at the point of connection of the third
  202. 7:47arrestor will not be the same as the one
  203. 7:49of the point of connection of the
  204. 7:51transformer because the lightning strike
  205. 7:52travels through the
  206. 7:53station propagates through the
  207. 7:56substation
  208. 7:58all right so some definitions many of
  209. 8:00them i've already discussed
  210. 8:02uh so you have the first thing which is
  211. 8:04called a direct lightning strike
  212. 8:06so it's when the lightning strike
  213. 8:08directly on the face
  214. 8:10of the transmission line without hitting
  215. 8:12the shielding wire
  216. 8:15the back flashover it's a flashover
  217. 8:17between
  218. 8:18ground and phase so when the lightning
  219. 8:20strike
  220. 8:21the neutral wire the top of the tower
  221. 8:24and you have
  222. 8:25i mean at the top of the tower or in
  223. 8:27between it doesn't matter
  224. 8:29um you will have the flash so you the
  225. 8:31voltage will rise
  226. 8:32then the voltage difference between the
  227. 8:35ground and the phase wire will be high
  228. 8:37and you will have a flashlight
  229. 8:38between so this is a backlash then you
  230. 8:41have the back flashover rate
  231. 8:43which is the number of back flashover of
  232. 8:45the line
  233. 8:46per 100 kilometers so you take a section
  234. 8:49of line
  235. 8:50per year so this will depend on the on
  236. 8:52the tower geometry
  237. 8:54and on the ground density of lightning
  238. 8:57in the region the grounds of like
  239. 8:59the ground density is how often you get
  240. 9:02lightning strikes
  241. 9:03for example if you are in uh you know in
  242. 9:06the
  243. 9:07louisiana region in the u.s here you
  244. 9:09have a very high lightning
  245. 9:11lightning strike ground density whereas
  246. 9:14if you are
  247. 9:15more up north you know in the west coast
  248. 9:17of canada it's much
  249. 9:20lower
  250. 9:22okay then we will see together how to
  251. 9:24determine what is called the critical
  252. 9:26current
  253. 9:27the critical current it's when you will
  254. 9:29apply a lightning strike during the
  255. 9:30simulation
  256. 9:31on at a certain point on the incoming
  257. 9:34line so typically you will have the
  258. 9:35substation
  259. 9:36all the incoming line the incoming line
  260. 9:39and you will put the lighting strike
  261. 9:41closed uh on the line close by the
  262. 9:44substation
  263. 9:45within few miles or even less you know
  264. 9:47hundreds of
  265. 9:48meters or miles you will put the
  266. 9:51lightning strikes here
  267. 9:53and the critical current will be the
  268. 9:55minimum
  269. 9:57peak current of this lightning strike
  270. 9:59which will
  271. 10:00cause a failure in the substation
  272. 10:04so for that you will have to know of
  273. 10:06course the wisdom label
  274. 10:08of all equipment which are called the
  275. 10:11bil
  276. 10:12the basic lightning impulse insulation
  277. 10:16level
  278. 10:18so you will need to know those values
  279. 10:20simulate the lightning strike monitor
  280. 10:22the voltage
  281. 10:23at at each point in the substation and
  282. 10:27see if the voltage reach
  283. 10:28this maximum level and if it's the case
  284. 10:31then
  285. 10:31you are above the critical current and
  286. 10:34so it will be
  287. 10:35we will run several simulations in order
  288. 10:37to determine the critical current at
  289. 10:39each point
  290. 10:40of the of this incoming
  291. 10:45actually line some point when you go
  292. 10:46further and further away from the
  293. 10:48substation
  294. 10:48this critical current become very high
  295. 10:50it can be more than 200 kilo amps
  296. 10:54at some point when it's over 200
  297. 10:56kilometers we
  298. 10:58are going to standard we assume that
  299. 11:00it's not possible anymore
  300. 11:02and so that's that means that such a
  301. 11:04lightning strike does not exist it's too
  302. 11:06high
  303. 11:06or it's uh the probability is much too
  304. 11:09low so you
  305. 11:10you you will say that at this point no
  306. 11:12lightning would
  307. 11:14uh no no lightning would create the
  308. 11:17damage in the substation
  309. 11:18and this this points this uh
  310. 11:21distance from the substation to
  311. 11:24on the line where you have you reach a
  312. 11:27critical current of 200 kilo amps
  313. 11:29it's called the critical distance we
  314. 11:32will see that uh
  315. 11:33earlier okay so we discussed here the
  316. 11:37bil the bsl
  317. 11:39um so the bil the definition is
  318. 11:42um it give a probability of
  319. 11:46the wisdom probability of 90 percent
  320. 11:50however you will see for if you watch
  321. 11:53the video of the switching
  322. 11:54insulation coordination it's a little
  323. 11:56different for lightning
  324. 11:58because basically the the level of
  325. 12:00lightning for
  326. 12:01the difference between ninety percent of
  327. 12:04winston and fifty percent of wisdom it's
  328. 12:05almost nothing
  329. 12:07and so typically for lightning because
  330. 12:09the statistical distribution of the
  331. 12:11width and voltage is so narrow
  332. 12:14even for internal or external insulation
  333. 12:17we will use
  334. 12:21just one a single level which will be
  335. 12:24the level to design or design
  336. 12:26and if you get an overvoltage above this
  337. 12:27level then
  338. 12:29you get you get a damage and all
  339. 12:32flash of backlash so it will be a bit
  340. 12:36easier than
  341. 12:37compared to switching where you have
  342. 12:39some equipment like insulators which are
  343. 12:41called non-self-restoring insulation
  344. 12:45and which have a which has a statistical
  345. 12:47behavior and forced us to
  346. 12:49cross different statistical roles
  347. 12:54okay so the limit distance is actually
  348. 12:56what i call before the critical distance
  349. 12:58i apologize the real name is limit
  350. 12:59distance
  351. 13:00so again this is when you apply
  352. 13:03lightning strikes on the line
  353. 13:05you find the critical distance and at
  354. 13:07some point
  355. 13:08the the critical current will be higher
  356. 13:10than 200 kilo amps so this is
  357. 13:13this point here is the limit distance we
  358. 13:14will repeat that again
  359. 13:17later to make sure it's clear
  360. 13:22okay so then you have what is called the
  361. 13:23maximum shielding
  362. 13:25current uh we will we will discuss
  363. 13:29what is the max maximum chilling current
  364. 13:31in the next slides
  365. 13:34just a quick introduction to that when
  366. 13:36you will see you have
  367. 13:37your phase conductor where they get
  368. 13:39protected by a shielding current
  369. 13:42and you will see the theory but
  370. 13:45the bottom line is for low
  371. 13:50lightning currents you are more likely
  372. 13:52to get a chilling failure than for
  373. 13:54a high lightning current and actually
  374. 13:57when the lightning current is very high
  375. 13:59you most of them you don't have shading
  376. 14:02failure
  377. 14:03and so the limit between that is the
  378. 14:04maximum shielding current it's the
  379. 14:06highest magnitude of lightning current
  380. 14:08which may cause a shielding failure
  381. 14:11so we will see the theory right after so
  382. 14:13don't worry if it's not so clear
  383. 14:24all right then you have the
  384. 14:25representative lightning stroke current
  385. 14:27which is the
  386. 14:28minimum value of lightning current at
  387. 14:30specific point of impact which produces
  388. 14:33over voltages that the equipment has to
  389. 14:35withstand
  390. 14:39right so then like i said you will do
  391. 14:42this study and you will
  392. 14:43come out with some line performance
  393. 14:46or so for line performance the outcome
  394. 14:49of the study will be the number of flash
  395. 14:51over
  396. 14:52per 100 kilometers and per year then for
  397. 14:55substation it will be
  398. 14:57the mean time between failure and so you
  399. 14:59have here some
  400. 15:00typical performance criterion here for
  401. 15:04ehv and hd system or here for
  402. 15:07different type of substation of course
  403. 15:10of course here there is an economical
  404. 15:12problem
  405. 15:13uh like it's a trailer between
  406. 15:15economical concern
  407. 15:17and failures um in order to increase
  408. 15:20the mean time between failure and the
  409. 15:22substation either
  410. 15:23you get equipment with higher bil
  411. 15:27which costs of course more which are
  412. 15:29more expensive
  413. 15:30or you put more surge arresters
  414. 15:33or you change the tower design so all
  415. 15:36that doesn't cost
  416. 15:37when you have one failure every 500
  417. 15:40years
  418. 15:41you know that's why you made me wonder
  419. 15:43why would i spend more money on that so
  420. 15:44it's really like a trade-off between
  421. 15:47economical concern and
  422. 15:52design
  423. 15:55okay so again how we are going to
  424. 15:59do that in the mtp so the first step
  425. 16:00will be to model completely the design
  426. 16:03so let's take a simple example where we
  427. 16:05have one substation with one incoming
  428. 16:07line
  429. 16:08so we are going to
  430. 16:12place a lightning strike
  431. 16:15for current source at the top of this
  432. 16:17line and at several points going further
  433. 16:19and further away
  434. 16:20for each point where we apply this
  435. 16:23current source
  436. 16:24we will we will vary
  437. 16:27the um the current the
  438. 16:30lightning strike peak current so we'll
  439. 16:33vary it in order to find
  440. 16:35the limit between failure or no failure
  441. 16:38if i have a peak current lower than this
  442. 16:42point i have no failure if i have a
  443. 16:43bigger
  444. 16:44higher than this point i have a failure
  445. 16:46so that's again the critical current
  446. 16:48you will be supposed to do that at each
  447. 16:50point on the line but of course to
  448. 16:52simplify it what we're going to do is to
  449. 16:53cut the line into section
  450. 16:56um very often what is done is we do that
  451. 16:58at each tower top
  452. 17:00but it's also common to do it at the
  453. 17:02tower top and at the middle of the line
  454. 17:04and so that's how you will
  455. 17:05sectionalize your line and apply the
  456. 17:08lightning strikes
  457. 17:09just because you cannot apply
  458. 17:10continuously it will be much
  459. 17:12way too much cases and it's not so
  460. 17:16relevant
  461. 17:18okay so after the mtp study you will
  462. 17:20have the critical
  463. 17:21current at each tower
  464. 17:25so
  465. 17:29if you if you do actually lightning on
  466. 17:31the cable system
  467. 17:32so of course the lightning will not
  468. 17:33strike the cable system but
  469. 17:35it may for example strike on the
  470. 17:37overhead line and then propagate
  471. 17:39through the cable system through um
  472. 17:42or through transformers or in this case
  473. 17:45it's the voltage between sheets and
  474. 17:47ground which
  475. 17:48which may cause the the flashover you
  476. 17:51may want to monitor also the arrestor
  477. 17:53energy
  478. 17:53so that's all the outputs of any of the
  479. 17:57mtp simulation
  480. 18:02okay so the lightning the lighting we
  481. 18:05have different lighting model in mtp
  482. 18:08the one recommended by standard is the
  483. 18:10sea gray model
  484. 18:12so the secret model has a certain shape
  485. 18:14um
  486. 18:15some people do studies with double
  487. 18:18exponential
  488. 18:19um it's not necessarily recommended to
  489. 18:21use that because
  490. 18:23um double exponentials are actually the
  491. 18:26the the surge the current surge which i
  492. 18:29use for testing
  493. 18:31uh but uh according to c grade iec
  494. 18:34it's recommended to use this remodel for
  495. 18:37lightning strike but
  496. 18:38both can be used the two models are they
  497. 18:40are here in the entp
  498. 18:45okay so now um
  499. 18:51okay so now let's discuss a little bit
  500. 18:53the tower geometry
  501. 18:55so remember i in the introduction i
  502. 18:58explained that
  503. 19:00when you have a lightning strike
  504. 19:01according to the lightning intensity
  505. 19:04you may hit the chilling wire or the
  506. 19:07phase and when you have a lower um
  507. 19:11low intensity you're more likely to hit
  508. 19:14the the face and have a shielding
  509. 19:17failure
  510. 19:18so why is that well it's because
  511. 19:21when you have a conductor or
  512. 19:24any metal metallic structure which is a
  513. 19:28conductor
  514. 19:29you have an attractive radius the
  515. 19:32attractive radius is
  516. 19:33a radius if a lightning strike enter it
  517. 19:37the lightning strike will end up on the
  518. 19:39metallic structure
  519. 19:41so having this uh chilling wire or
  520. 19:44sometimes you have two i think those
  521. 19:46create kind of like a cylinder
  522. 19:48over the line and if the lightning
  523. 19:50strike until the cylinder
  524. 19:52it goes into the shielding wire and this
  525. 19:56circle this uh attractive radius
  526. 19:59depends on the the lightning current
  527. 20:03intensity
  528. 20:04and so for low intensity
  529. 20:08for low intensity lightning strike you
  530. 20:10will have a smaller radius
  531. 20:12whereas for high intensity lightning
  532. 20:14strike you have a very large radius
  533. 20:16and that's why this large radius of the
  534. 20:18on the conductors at the top of the
  535. 20:20tower we basically cover the entire line
  536. 20:22and protect
  537. 20:23completely the line i will show you a
  538. 20:24drawing after which will
  539. 20:26and repeat the explanation
  540. 20:41okay so then the the so the lightning
  541. 20:44distance
  542. 20:45is the distance between an object on
  543. 20:47earth and a lightning
  544. 20:48leader within which the lightning
  545. 20:51must approach before the
  546. 20:55point of strike is determined
  547. 20:59and so for this um for for this
  548. 21:03attractive radius you have several
  549. 21:04models that exist in the literature
  550. 21:07um some of them depend on the current
  551. 21:10some of them depend also on the height
  552. 21:12so it may depend on both height and
  553. 21:15current
  554. 21:19okay so those are important factors to
  555. 21:21consider when the tower will be designed
  556. 21:23and
  557. 21:23determine again the the
  558. 21:26the mean time between failure underlying
  559. 21:28performance
  560. 21:32so also if the goal is to determine
  561. 21:36how much lightning is going to strike
  562. 21:38your line okay so
  563. 21:40try to imagine to see a single the line
  564. 21:43from the top you have the
  565. 21:44chili wires and those ceiling wires
  566. 21:47create
  567. 21:48a cylinder an attractive radius so a big
  568. 21:51cylinder
  569. 21:52and when you know the regional brand
  570. 21:53density so how much lightning strikes
  571. 21:56per year
  572. 21:57and you see this the ground cover
  573. 22:00from this line and seeing from the top
  574. 22:02that's how you can calculate how many
  575. 22:04lightning will strike your line per year
  576. 22:06and of course this will depend again on
  577. 22:08the lighting density because the
  578. 22:09lightning density will unlock
  579. 22:11the larger radius
  580. 22:16okay so let's put a drawing behind all
  581. 22:17that so it's easier to understand
  582. 22:20here you have your transmission line
  583. 22:22with phase a
  584. 22:23b and c here you have two chilling wires
  585. 22:28then you have here your attracted ray
  586. 22:31attractive radius
  587. 22:33okay so you see the attractive radius
  588. 22:36here you have
  589. 22:37the equation which is yours actually
  590. 22:39which will be used here for the
  591. 22:41for the webinar today which is the ritz
  592. 22:43from april
  593. 22:44and this one depends on the height and
  594. 22:47the current
  595. 22:49okay so assume any lightning strike for
  596. 22:52example 100
  597. 22:53amps lightning strike so you have i you
  598. 22:56have the tau the height of this
  599. 22:57conductor and that's how you calculate
  600. 22:59the radius
  601. 23:00then you have this radius here you do
  602. 23:02the same thing called the second shield
  603. 23:04wire
  604. 23:05and you have this second radius here do
  605. 23:07the same thing for the phase
  606. 23:09and you have here the radius around the
  607. 23:10face
  608. 23:12for a low current here you see that you
  609. 23:14will have a possibility
  610. 23:15the lightning lightning leader is coming
  611. 23:17from the top here of course coming from
  612. 23:19the top
  613. 23:20if it enters this zone which is the
  614. 23:22striking distance
  615. 23:23it will end up in the on the conductor
  616. 23:26whereas if you enter this zone it will
  617. 23:29end up there
  618. 23:30and if the lighting and density is very
  619. 23:32high
  620. 23:33rc is going to increase and so here b
  621. 23:36will end up coming in top of a
  622. 23:39and so then you will have no chance for
  623. 23:41any lightning
  624. 23:42to go to uh to go on the on the face and
  625. 23:45so you will have no chilling failure
  626. 23:49okay so this is called the um
  627. 23:53whatever all right so yes so that's um
  628. 23:58on the geometry point of view so that's
  629. 23:59what is in poland so in a
  630. 24:01in a country where i don't have so much
  631. 24:03ground uh
  632. 24:04while you have a very low height where
  633. 24:07you have a very low
  634. 24:09um ground density of lightning
  635. 24:12you will have only one chili wire at the
  636. 24:14in the middle
  637. 24:15and so basically if you have a very high
  638. 24:17lighting strike you will have very
  639. 24:19large radius which will protect your
  640. 24:20line but for lower
  641. 24:23level of lightning strike sometimes you
  642. 24:26will have chilling failure but it's okay
  643. 24:27because a
  644. 24:28lower level of lightning intensity and
  645. 24:31so they may not cause a damage
  646. 24:33that's the whole point of doing the
  647. 24:34study here
  648. 24:44okay so if if we repeat a little bit the
  649. 24:47procedure here
  650. 24:49and for that i will pop a
  651. 24:52an emtp example
  652. 24:56okay so here you have a simplified model
  653. 24:58of substation and we come back to that
  654. 25:01we never apply a lightning strike on the
  655. 25:03substation because we assume the
  656. 25:04substation is protected by
  657. 25:07lightning mass tents which will capture
  658. 25:09every lightning possible
  659. 25:11trying to strike the substation so what
  660. 25:13here
  661. 25:14that is the end of the substation on
  662. 25:15this side and so we this tower is still
  663. 25:18protected in the substation
  664. 25:19so we start applying lightning strike on
  665. 25:22the line
  666. 25:24here in our case we will try to apply on
  667. 25:26each tower so here you see three
  668. 25:28lightning strikes but it's actually one
  669. 25:29after the other
  670. 25:30so let first so we can forget those two
  671. 25:33here and actually delete them so first
  672. 25:37we
  673. 25:38we apply on the first hour we vary the
  674. 25:41intensity
  675. 25:42so we have no failure in here so we
  676. 25:45monitor the voltage
  677. 25:47uh if the overvoltage during the
  678. 25:48simulation remain below the bils it
  679. 25:50means there is no failure if it goes
  680. 25:52above there is a failure it means there
  681. 25:53is a failure
  682. 25:54so we'll vary for example for this point
  683. 25:57we will get
  684. 25:5875 kilo amps for failures
  685. 26:01but so if this is the limit if i apply a
  686. 26:04lightning strike below 75
  687. 26:06there is no failure and if i apply a
  688. 26:09lightning strike above
  689. 26:1175 there is a failure now it means 75 is
  690. 26:15my critical current
  691. 26:17then i go and i will assume it's the
  692. 26:19same critical current for all
  693. 26:20this section for the line here and for
  694. 26:22half the line here
  695. 26:24then i will place this lightning strike
  696. 26:27on the next
  697. 26:28next hour and do the same thing because
  698. 26:31i'm further away
  699. 26:32here now the like the um the critical
  700. 26:35current will be a bit higher
  701. 26:36maybe 100 and i would assume it's the
  702. 26:39same critical current for all that
  703. 26:41if you don't like this assumption you're
  704. 26:43free to apply the lightning in between
  705. 26:45and cut this line into section and apply
  706. 26:48the lighting in between
  707. 26:49and i will go like that step by step
  708. 26:51until the critical current is above 200
  709. 26:54kilo amps
  710. 26:54then like we said we assume this is a
  711. 26:58case which has
  712. 26:58the probability which is too low to be
  713. 27:01considered and so
  714. 27:02now we have our critical distance so for
  715. 27:05example let's assume
  716. 27:06here the critical current is 210
  717. 27:10okay then it means we don't consider
  718. 27:12this tower and
  719. 27:14the critical distance will be the length
  720. 27:16of all those sections those spans
  721. 27:18up to this half line
  722. 27:22okay so that will be the first step to
  723. 27:23find the critical current at each point
  724. 27:26then what do you do with that
  725. 27:30then you determine the number of
  726. 27:31children failure
  727. 27:33so it will depend of several things the
  728. 27:35ground
  729. 27:36density the what we call here
  730. 27:41in ng the regional ground flash density
  731. 27:45multiplied by l1 l1
  732. 27:48is the length of the line so the total
  733. 27:52length of the line
  734. 27:53and um gc is
  735. 27:56the exposure distance here actually i
  736. 28:00sorry i wasn't so cute and i got decided
  737. 28:03myself as well
  738. 28:04here what in this slide what we show is
  739. 28:06how to determine the shielding failure
  740. 28:09so the changing failure the goal here is
  741. 28:12to find
  742. 28:13the maximum current which may create
  743. 28:16achieving failure
  744. 28:18okay so you understand that as you
  745. 28:19higher i
  746. 28:22the the radius here increases and at
  747. 28:24some point d
  748. 28:25becomes zero so that's the goal here is
  749. 28:27to find
  750. 28:29what is the maximum current which may
  751. 28:31create a
  752. 28:32shielding failure so that's how we do
  753. 28:34that
  754. 28:35we find um we calculate basically here
  755. 28:41the the limits so the limit will be i m
  756. 28:45i am for which there is no d
  757. 28:48equals zero and then we'll do an
  758. 28:50integral of
  759. 28:52the length of the line multiply by d
  760. 28:55which is here multiply by two of course
  761. 28:58because it's
  762. 29:00two sides and um
  763. 29:03and then the uh the so the lens
  764. 29:06d multiplied by two and the ground
  765. 29:08density so you have this equation here
  766. 29:10you do the integral from
  767. 29:13the critical current to
  768. 29:17the critical current to the maximum
  769. 29:19chilling failure and that's how you get
  770. 29:21the shielding failure rate
  771. 29:24okay so the critical current is
  772. 29:26calculated
  773. 29:27um it's calculated by emtp so you get
  774. 29:31those critical current the way we
  775. 29:32explained
  776. 29:34and you can do that for the line the
  777. 29:36critical current here
  778. 29:37will depend on the section so you may do
  779. 29:40this per section and get the chilling
  780. 29:42failure
  781. 29:42per section and add them up together
  782. 29:48as a if you if you'd like to
  783. 29:51simplify your life you may also here
  784. 29:54calculate
  785. 29:55the chilling current like that if you
  786. 29:57know the third impedance of the line
  787. 29:59you may calculate here you may just use
  788. 30:03this calculation and
  789. 30:04without doing the simulation in empty
  790. 30:08here when we determine the shielding
  791. 30:10failure it's actually for the line
  792. 30:12performance
  793. 30:13so that's why in this calculation we
  794. 30:15don't reconsider the substation
  795. 30:17we consider u50 which is the critical
  796. 30:21flash over the critical flash over
  797. 30:23voltage of the line
  798. 30:25and so we just assume the failure on the
  799. 30:27line okay so when you
  800. 30:29have this chilling failure rate you only
  801. 30:31focus on the line
  802. 30:33then the goal is to focus on the
  803. 30:34substation you
  804. 30:36consider the critical current
  805. 30:40of which will create the flashover in
  806. 30:42the substation
  807. 30:46okay so here by design if you want
  808. 30:48perfect shielding then you have to set
  809. 30:51here the critical current equal to i m
  810. 30:53or
  811. 30:54you have to as um you have to arrange
  812. 30:57the geometry of the line so i
  813. 30:58am which is the value of intensity
  814. 31:02where d is zero to make sure that
  815. 31:06i am equal i c
  816. 31:17all right so now let's quickly discuss
  817. 31:19how to
  818. 31:20model everything in emtp so first of all
  819. 31:24a lightning study is something very
  820. 31:27local
  821. 31:28because it is local
  822. 31:31you don't need to model the entire
  823. 31:34system of the country to study lightning
  824. 31:37it's mostly you will
  825. 31:41you will model everything in the radius
  826. 31:44of a few miles or few kilometers
  827. 31:46close to the substation where you want
  828. 31:48to analyze lightning
  829. 31:50so if we take a look quickly here at an
  830. 31:52empty model
  831. 31:54you have the substation here we assume
  832. 31:55there is only one incoming line to
  833. 31:57have a simplified case but in reality
  834. 31:59you may have zero
  835. 32:00and you see here we have several steps
  836. 32:04and at some point we don't model anymore
  837. 32:08when we stop modeling there is one thing
  838. 32:11important to do
  839. 32:12when you apply your lightning on the
  840. 32:14tower for example let's say here you
  841. 32:16move this lightning and you put it
  842. 32:20at this point when you apply the
  843. 32:24lightning you know the lightning strike
  844. 32:25will create
  845. 32:26a search a search voltage the search
  846. 32:29voltage will travel through the line and
  847. 32:31reflect
  848. 32:32of course here if you stop modeling here
  849. 32:35you have to make sure when you play the
  850. 32:36lightning strike that it doesn't come
  851. 32:38here and
  852. 32:39come back that it doesn't go here and
  853. 32:40come back so what we typically do for
  854. 32:43that
  855. 32:44is we will here put a section of
  856. 32:47transmission line which is
  857. 32:49long enough so the lightning never comes
  858. 32:51back
  859. 32:52so typically you will put 50 kilometers
  860. 32:54or 20 kilometers and that should be
  861. 32:56enough
  862. 32:57the second strategy is to use a negative
  863. 32:59voltage source with
  864. 33:00an impedance which is equal to the surge
  865. 33:04impedance of the line
  866. 33:06but again to simplify in my opinion the
  867. 33:08easiest is to take the same transmission
  868. 33:10line here but
  869. 33:11generate it for a very long uh
  870. 33:14a very long section of 20 or 50
  871. 33:17kilometers
  872. 33:18and when so when you do the simulation
  873. 33:20the lightning strikes goes there and
  874. 33:22never have time to come back before the
  875. 33:23end of the simulation
  876. 33:26okay so that's how you will model
  877. 33:27boundaries in your system
  878. 33:29uh you put an ideal voltage source
  879. 33:33it's a good idea also to adjust here the
  880. 33:36phase
  881. 33:36angle to get worse case right so
  882. 33:39basically
  883. 33:40when you do the simulation uh you do one
  884. 33:43simulation and you
  885. 33:44you adjust your voltage source to get
  886. 33:46the maximum
  887. 33:47overvoltage in the substation and then
  888. 33:49you keep them like this
  889. 33:53so this is something you do at the
  890. 33:54beginning then once you have determined
  891. 33:56what's the worst case
  892. 33:58you just keep it like that
  893. 34:07all right then the for transmission
  894. 34:09lines um
  895. 34:10it's recommended to use a frequency
  896. 34:12dependent model or even better white
  897. 34:14damp models
  898. 34:15so i to uh to model them i don't go too
  899. 34:18much into detail we have specific videos
  900. 34:20on how to create transmission lines
  901. 34:23one thing here is that you see we model
  902. 34:25each span
  903. 34:26individually so you have
  904. 34:29so typically for a switching study or
  905. 34:33other type of study with modeled
  906. 34:34entire line in one device
  907. 34:38but here it's really each section so you
  908. 34:40will have
  909. 34:41the three phases and the chilling wires
  910. 34:44in this example we have only one shield
  911. 34:45wire
  912. 34:46you see it's here number one and then
  913. 34:48you have phase a b
  914. 34:49and c and so we repeat this section
  915. 34:53several times
  916. 34:54so that's how you do that then you also
  917. 34:56need to model the tower
  918. 34:58we'll come back on the tower model later
  919. 35:00but we will have to do it
  920. 35:02basically for that we use a lossless
  921. 35:05propagation line
  922. 35:07with a footing resistance we'll see
  923. 35:08after which is a cp model
  924. 35:12very often actually when you try to
  925. 35:14create a frequency dependent model
  926. 35:16or a wideband model for a very short
  927. 35:18section of line so one span which is you
  928. 35:20know 100 meters or so
  929. 35:22or sometimes more sometimes often it's
  930. 35:25very tough
  931. 35:26for the frequency dependent algorithm to
  932. 35:28fit that
  933. 35:29and you it may not be able to fit it or
  934. 35:32may require
  935. 35:33a very very high number of poles to do
  936. 35:35that and create numerical problems
  937. 35:38if that happens one thing that can be
  938. 35:39done is instead of
  939. 35:41generating a frequency dependent model
  940. 35:43of line you enter all the power
  941. 35:45configurations so the position of each
  942. 35:47conductor
  943. 35:48on space and all that but instead of the
  944. 35:51running the fd you generate
  945. 35:52a constant parameter line and you
  946. 35:56generate that for uh 50 kilohertz
  947. 36:00so the parameters resistance and
  948. 36:01backhands capacitance are
  949. 36:03evaluated for 50 kilohertz
  950. 36:07it's it's okay in one sense because i
  951. 36:09mean it's trying to work like that
  952. 36:11because the lightning strike is
  953. 36:12very high frequency the other frequency
  954. 36:15presents during the study is the syst
  955. 36:17the 60 hertz or 50 hertz frequency which
  956. 36:20for such a speed it looks like a dc
  957. 36:23voltage in here so that's why it's fine
  958. 36:25to do that
  959. 36:28if you study if the if you want to be
  960. 36:31very precise
  961. 36:32you may also model the corona effect
  962. 36:36the corona effect will give a capacitive
  963. 36:40behavior to your line which will
  964. 36:43lower the stiffness of the
  965. 36:46of the overvoltage so it's a good idea
  966. 36:48to use that if you want to be precise
  967. 36:50especially for very high voltage
  968. 36:52if you don't you will be conservative so
  969. 36:54it's fine as well
  970. 36:58okay so for air gap it's uh it's
  971. 37:01important to model the air gap
  972. 37:03of course because that's what will
  973. 37:04create the
  974. 37:06the flashover so when the air gap is
  975. 37:09short
  976. 37:10you can assume that as soon as there is
  977. 37:12a
  978. 37:13flashover it's like an ideal switch
  979. 37:16closing
  980. 37:17whereas if it's a long air gap more than
  981. 37:19one meter then it's
  982. 37:21important to reproduce the leader
  983. 37:22propagation which we add more delay and
  984. 37:25add an impedance to this
  985. 37:26arc
  986. 37:30okay now how do we model the substation
  987. 37:33itself
  988. 37:34everything must be modeled basically
  989. 37:36each section of conductor
  990. 37:38must be modeled if it's more than 10
  991. 37:40meters
  992. 37:41so approximately 30 feet then you should
  993. 37:44use a cp line
  994. 37:46so for the cp line we will enter the
  995. 37:48characteristic impedance
  996. 37:50and the length of this line then you can
  997. 37:53assume
  998. 37:54a traveling wave
  999. 37:57the propagation speed
  1000. 38:01of about 80 of the speed of light
  1001. 38:06this is for air insulated substation for
  1002. 38:08gas insulated substation it may be
  1003. 38:10slightly different
  1004. 38:14then if you have a conductor shorter
  1005. 38:16than that
  1006. 38:17then simply use a pendant
  1007. 38:20with a typical value of one micro henry
  1008. 38:23per meter
  1009. 38:26for gis typically the
  1010. 38:30surge impedance is about 60 to 80 ohm
  1011. 38:34for those sections of line whereas for
  1012. 38:36air insulated substation it could be 150
  1013. 38:38200
  1014. 38:42then you have to place the surge
  1015. 38:44capacitance of
  1016. 38:45every single equipment if you have a bus
  1017. 38:48bar
  1018. 38:48you have to put the street capacity of a
  1019. 38:50transformer a
  1020. 38:52ct open breaker or clothes breaker
  1021. 38:56every single equipment has to be
  1022. 38:57represented by a three capacitance
  1023. 39:00you can find typical value of three
  1024. 39:01capacitance in is standard
  1025. 39:04we actually have a device which is
  1026. 39:06called a stray capacitance which is a
  1027. 39:08library
  1028. 39:09database or stray capacitance so you can
  1029. 39:11use this device as well
  1030. 39:16okay so it's the same for transformers
  1031. 39:19to
  1032. 39:19it's possible actually to be even more
  1033. 39:21precise for transformer and to use
  1034. 39:23a high frequency model of transformer
  1035. 39:26so if you have done a frequency test
  1036. 39:28where the
  1037. 39:29the open circuit impedance of the
  1038. 39:32transformer is measured for a wide range
  1039. 39:34of frequencies
  1040. 39:35then you may get this impedance data
  1041. 39:37impedance that source frequency and
  1042. 39:39create
  1043. 39:40a frequency dependence impedance to
  1044. 39:42reproduce
  1045. 39:43your transformer so that's uh that's
  1046. 39:46something
  1047. 39:46feasible often it's not done for
  1048. 39:50for lightning studies because it's a lot
  1049. 39:51of work but to be precise it's possible
  1050. 39:53to do that
  1051. 39:57for such arresters it's very important
  1052. 39:59here to use a frequency dependent model
  1053. 40:01of soldier resistor
  1054. 40:02so there is a specific video on how to
  1055. 40:05create those frequency dependent model i
  1056. 40:07will come back to them
  1057. 40:08quickly after but yeah keep that in mind
  1058. 40:11and the lightning source also is a sig
  1059. 40:14resource
  1060. 40:15the lightning current source is a secret
  1061. 40:16source
  1062. 40:20okay so at the end of the day if you see
  1063. 40:21a substation like that it will look like
  1064. 40:23this where you have
  1065. 40:25any time you have here a conductor you
  1066. 40:27will model it with
  1067. 40:28a cp line here even very short
  1068. 40:31conductors were modeled with cp9 three
  1069. 40:34meters it's okay
  1070. 40:35it will force to use a very small time
  1071. 40:37step
  1072. 40:38to simulate that but it's extra
  1073. 40:40precision
  1074. 40:42you see that each equipment are modeled
  1075. 40:44by a capacitance
  1076. 40:46and you have surgery so that's
  1077. 40:53okay so the lightning strike here you
  1078. 40:55can find it
  1079. 40:56if you go to um
  1080. 41:00if you go to sources here you can grab
  1081. 41:03what is called seed currency so this is
  1082. 41:06our lightning strikes
  1083. 41:08even better what i would recommend you
  1084. 41:09to do is to use this example which is
  1085. 41:12available on our exchange platform you
  1086. 41:15can
  1087. 41:15contact the technical support to get it
  1088. 41:18and
  1089. 41:19to use this model because in this model
  1090. 41:20you only enter
  1091. 41:22the uh the peak current of lightning
  1092. 41:25strike for example here 10 000
  1093. 41:28and automatically it will adjust all
  1094. 41:31other parameters so the stiffness and
  1095. 41:34the tail duration
  1096. 41:36so it's it's pretty nice you don't need
  1097. 41:37to
  1098. 41:39you don't need to calculate or latch
  1099. 41:40yourself
  1100. 41:46okay so it's uh the current source looks
  1101. 41:47like this so you have several parameters
  1102. 41:50the peak current uh you have the
  1103. 41:53time the tf here which is uh
  1104. 41:56well you can see what it is in the in
  1105. 41:58this figure
  1106. 41:59uh you have uh the stiffness
  1107. 42:02this is kind of important and a major
  1108. 42:04difference compared if you do the
  1109. 42:06lightning strike using this model
  1110. 42:08compared to a double exponential model
  1111. 42:10uh the stiffness will not be the same
  1112. 42:12and as you know the stiffness of current
  1113. 42:14has a huge impact on overvoltage so
  1114. 42:17that's why
  1115. 42:18it's recommended to use this model
  1116. 42:23also typically in the lightning strike
  1117. 42:25model we put a resistance in parallel
  1118. 42:28and that's what we've done here in this
  1119. 42:29little model you have
  1120. 42:32the secretable with this in parallel
  1121. 42:44okay so here you have some equations on
  1122. 42:47how to calculate
  1123. 42:49uh current stiffness and all the
  1124. 42:51parameters
  1125. 42:53um if you hear the actually that's the
  1126. 42:56the summary of it so the current
  1127. 42:58the stiffness that tells you the
  1128. 43:00calibration and
  1129. 43:01the time to get some t
  1130. 43:05t30 i don't remember what it is
  1131. 43:12it's a tf
  1132. 43:15okay so you have everything you need
  1133. 43:17here i'm not sure about td30 but
  1134. 43:19what you need really is i sm th
  1135. 43:22and i would have to double check if t30
  1136. 43:27is
  1137. 43:27tf not sure about that it's actually
  1138. 43:30written in the
  1139. 43:32in the script of this device here
  1140. 43:35let's see if we can quickly find out
  1141. 43:38find that out till team
  1142. 43:58not sure if uh td30 is actually used in
  1143. 44:01the model oh yeah it is td30
  1144. 44:11no i don't think td sort is actually
  1145. 44:13used in the model itself
  1146. 44:15it's just another parameter
  1147. 44:18apologize i don't remember what it is
  1148. 44:20exactly
  1149. 44:23all right so then um then you need to
  1150. 44:26model the tower
  1151. 44:28okay let me keep going on the tower so
  1152. 44:30the tower you will approximate that it's
  1153. 44:32a cylinder
  1154. 44:33and then you will model you will
  1155. 44:36calculate
  1156. 44:37the surge impedance based on
  1157. 44:41the parameter of this of this cylinder
  1158. 44:44okay so the average radius uh the
  1159. 44:46section
  1160. 44:47here h1 h2 if the
  1161. 44:50radius is if the radius is changing
  1162. 44:59okay so then what the way you are going
  1163. 45:01to model that is to use a cp line
  1164. 45:04in the cp line you put the surge
  1165. 45:06impedance the propagation speed of 80
  1166. 45:1080 of speed of light and that's how you
  1167. 45:12will model this tower
  1168. 45:16let me show you how it is
  1169. 45:21okay so you see here that's our tower um
  1170. 45:25before actually showing you that let me
  1171. 45:26show you a little example a drawing
  1172. 45:28you see you have a tower here and so you
  1173. 45:30have different
  1174. 45:32sections for each sections here
  1175. 45:36and the arms are also model however
  1176. 45:38because the arm are very short
  1177. 45:41we only use inductances for that it's up
  1178. 45:44to you
  1179. 45:44you may use cp line or inductances you
  1180. 45:46may do the calculation the same
  1181. 45:48calculation for the arms
  1182. 45:49it's fine to use conductances else
  1183. 45:52typically it's a one micro henry per
  1184. 45:54meter
  1185. 45:55for those sections okay so this
  1186. 45:58is our transmission line here you have
  1187. 46:00all the faces so
  1188. 46:01phase a b and c for example and the top
  1189. 46:04here is the tower top so the chilling
  1190. 46:06wire
  1191. 46:06that's where we'll apply the lightning
  1192. 46:08strike so when we apply the lightning
  1193. 46:10strike you see that it will travel
  1194. 46:11through the line
  1195. 46:13it may create an overvoltage between
  1196. 46:14here the a phase and an overvoltage and
  1197. 46:17this is the air gap model where
  1198. 46:19you may have a flashover and here you
  1199. 46:22have the
  1200. 46:23grounding pin of the of the tower where
  1201. 46:26we will
  1202. 46:27model the grounding resistance
  1203. 46:30okay so the grounding resistance is
  1204. 46:32modeled as such
  1205. 46:34when you have a lightning strike you
  1206. 46:36have a lot of current going
  1207. 46:37through the ground inside the ground and
  1208. 46:39these create what is called ionization
  1209. 46:42which will vary the resistance
  1210. 46:45the grounding resistance and this is
  1211. 46:48here the equation
  1212. 46:49provided by a triple e for the grounding
  1213. 46:51resistance
  1214. 46:52so you have here it depends on the
  1215. 46:55lightning density and
  1216. 46:56ig and ig the parameter calculated which
  1217. 46:59depends
  1218. 47:00on the solar resistivity mostly and
  1219. 47:05the footing resistance of at 60 hertz so
  1220. 47:08this may be determined
  1221. 47:10by measurements and the solution
  1222. 47:13gradient so here we typically take this
  1223. 47:15value 400.
  1224. 47:17how do we model that now well we just
  1225. 47:19create a small control circuit
  1226. 47:21we use this controlled uh
  1227. 47:24norton equivalent where we set i
  1228. 47:28the current at zero the whole time so
  1229. 47:30basically it's just a control resistance
  1230. 47:33and you see we measure here the current
  1231. 47:36then we have the equation i just show
  1232. 47:39here
  1233. 47:40you the input u2 which is the footing
  1234. 47:43resistance multiplied by square root of
  1235. 47:46two
  1236. 47:47one plus the current u1 divided by
  1237. 47:5118 500 so that's exactly
  1238. 47:55this equation here
  1239. 47:59okay and so this will control the
  1240. 48:02resistance
  1241. 48:03and here we have a small selector when
  1242. 48:06the intensity
  1243. 48:07is lower than 18 500
  1244. 48:10then we consider instance is the
  1245. 48:14footing resistance and when it's higher
  1246. 48:16we
  1247. 48:17use this uh this calculation
  1248. 48:20okay so it's just a selector okay so
  1249. 48:23that's how we model that
  1250. 48:24again this tower model is available
  1251. 48:27on demand so if you have a lightning
  1252. 48:29study to do you simply use that and
  1253. 48:31modify it
  1254. 48:35this example is actually inside the mtp
  1255. 48:37example
  1256. 48:44right so now let's discuss how do we
  1257. 48:47model those insulators
  1258. 48:50like i said you have two possibilities
  1259. 48:53which will mainly depend on the length
  1260. 48:55of the
  1261. 48:57insulator there is one the first method
  1262. 49:00is
  1263. 49:01when you have a voltage time curve which
  1264. 49:03means that the insulator will be able to
  1265. 49:05withstand a certain voltage for a
  1266. 49:07certain time only and after this time
  1267. 49:09you will have the backlash over
  1268. 49:10so the breakdown you may have this curve
  1269. 49:13here
  1270. 49:14then one way you can do that is again
  1271. 49:17the same way we've done for the
  1272. 49:18resistance
  1273. 49:19uh use a control um
  1274. 49:23use a control circuit to determine that
  1275. 49:26so you will enter those points
  1276. 49:28in a table and measure the current
  1277. 49:32create a timer and when you reach the
  1278. 49:35curve
  1279. 49:35basically close the gap it's possible to
  1280. 49:38do that but it's
  1281. 49:39not really what we recommend it's
  1282. 49:41possible to do it but
  1283. 49:43i will show you after other way to do it
  1284. 49:45which are easier
  1285. 49:47so the other model which is recommended
  1286. 49:49actually
  1287. 49:50is for gaps which are lower than
  1288. 49:541 meters or 1.2 meters
  1289. 49:58so here it uses an equation to determine
  1290. 50:00if there is a flashover or not
  1291. 50:02so it's used area criterion model so
  1292. 50:05according to the length
  1293. 50:07the the size of your gap okay you have
  1294. 50:10those parameters and you can interpolate
  1295. 50:12in between
  1296. 50:14and then automatically the model can
  1297. 50:16continuously integrate
  1298. 50:18the difference between v-gap and v0 so
  1299. 50:21the voltage
  1300. 50:22in the in the gap in the at the
  1301. 50:25insulator terminal
  1302. 50:27versus v0 here and when these integral
  1303. 50:31becomes larger than d
  1304. 50:32it's have a closed ideal switch so the
  1305. 50:36current will now go through the
  1306. 50:38uh goes through this gap and the voltage
  1307. 50:41on the phase
  1308. 50:42and the neutral and the ground will be
  1309. 50:44the same
  1310. 50:46okay so this model is valid for um
  1311. 50:49it's valid for a smaller gap and you can
  1312. 50:52find it here in the library
  1313. 50:55switches and it's called
  1314. 50:58um air gap
  1315. 51:02all right so that's the model we use
  1316. 51:04here in the slime model
  1317. 51:05it's right there
  1318. 51:12okay the second model to use you can use
  1319. 51:15it's for
  1320. 51:16larger gaps more than one meters more
  1321. 51:19than one meter
  1322. 51:20so this one is uh now reproduce the
  1323. 51:23leader propagation
  1324. 51:24okay so it will actually take when there
  1325. 51:27is a flashover it will take some time
  1326. 51:29for the flashover to go from this point
  1327. 51:30to here and
  1328. 51:31there will be a resistance associated
  1329. 51:35with that
  1330. 51:36so here the equation is written there
  1331. 51:39the only input for this model will be
  1332. 51:41the lens and the mall is already built
  1333. 51:44in emtp
  1334. 51:45so you can simply grab it from the
  1335. 51:47library
  1336. 51:48you have here an example if you go to
  1337. 51:51application
  1338. 51:52air gap leader okay the model is there
  1339. 51:56and you can select here the lens
  1340. 52:02okay so again this one is recommended to
  1341. 52:03be used when you have a lens high
  1342. 52:05higher than one meter
  1343. 52:09okay so then you have the software store
  1344. 52:11model
  1345. 52:12here again we did a i repeat we did a
  1346. 52:14complete video
  1347. 52:16on how to model such arresters for
  1348. 52:19lightning
  1349. 52:20it's important to use the frequency
  1350. 52:22dependence of resistor
  1351. 52:24so the frequency dependence of the
  1352. 52:25restore is model like this as a
  1353. 52:27combination of
  1354. 52:28rlc component and
  1355. 52:32two nonlinear resistance which have an
  1356. 52:34exponential
  1357. 52:35fitting there is a procedure in order to
  1358. 52:39build that
  1359. 52:40we actually have a device which does it
  1360. 52:42automatically for you
  1361. 52:44so the only things you will enter are
  1362. 52:46the uh
  1363. 52:47the impulse test
  1364. 52:51results so you have what is called v10
  1365. 52:54which is the voltage for a lightning
  1366. 52:57serve of 10 kilo amps
  1367. 52:59the lightning surge takes eight
  1368. 53:01microseconds to go to the peak
  1369. 53:03and 20 microseconds to go to the top so
  1370. 53:06it's a
  1371. 53:07820 so you need this value
  1372. 53:11and you need also a switching search so
  1373. 53:13a switching surge which
  1374. 53:15has you know for example a 30 60 so
  1375. 53:18third takes 30 seconds to go from zero
  1376. 53:21to the peak
  1377. 53:22and then 60 microseconds sorry
  1378. 53:24microseconds for the tail
  1379. 53:26so you need those two uh informations to
  1380. 53:29build this model
  1381. 53:30it's basically some fitting so we'll
  1382. 53:32adjust those characteristics to match
  1383. 53:35the switching uh pulse and then we'll
  1384. 53:38adjust l1 here
  1385. 53:39to match the lightning test and so then
  1386. 53:42this
  1387. 53:43surge arrester is valid for switching
  1388. 53:44and lightning so that's the one
  1389. 53:46recommended
  1390. 53:47i really invite you to take a look at
  1391. 53:48the video that we've done on server
  1392. 53:50store modeling to do that
  1393. 53:52and download in our exchange platform
  1394. 53:54the add-on which does
  1395. 53:56all that automatically yeah so this um
  1396. 54:00this model you enter basically all the
  1397. 54:02information you need
  1398. 54:04actually for that you also need to know
  1399. 54:05the number of columns in parallel and
  1400. 54:08the length of the surge arrester okay so
  1401. 54:11you enter all that in here
  1402. 54:13and it will automatically create this
  1403. 54:14model for you so
  1404. 54:16fairly easy at the end of the day
  1405. 54:23okay so here you have the way it's it's
  1406. 54:25built if you want to do it yourself
  1407. 54:29okay so this we discussed already the
  1408. 54:30voltage source where you put a long
  1409. 54:32transmission line to avoid reflection
  1410. 54:40okay so let's sum up one more time uh
  1411. 54:43what you have to do
  1412. 54:44so the first thing will be to uplink the
  1413. 54:46like apply lighting strike at default
  1414. 54:48points to determine the critical
  1415. 54:50current at um at each step
  1416. 54:54when you try to find a critical current
  1417. 54:57you compare the maximum voltage
  1418. 54:59with the bil of each equipment
  1419. 55:02but actually remember that we have to
  1420. 55:04consider the bil with
  1421. 55:06some safety coefficient safety factor
  1422. 55:08amplitude
  1423. 55:10correction factor and all that so what
  1424. 55:12you're going to do is
  1425. 55:14when you monitor the overvoltage instead
  1426. 55:17of comparing with the bil you will
  1427. 55:18compare to the bill divided by
  1428. 55:20all these coefficients so safety
  1429. 55:24coefficient
  1430. 55:24safety factor atmospheric correction
  1431. 55:27factor and altitude factor the
  1432. 55:29atmospheric correction factor depends on
  1433. 55:31the pollution mostly
  1434. 55:33right so all that take a look at the
  1435. 55:37you know for the ieee or iec standard to
  1436. 55:40see what the value of those coefficients
  1437. 55:41how to find them
  1438. 55:42we had a lot of references in the origin
  1439. 55:45and
  1440. 55:46classification of all hbo
  1441. 55:49and so then when you have this um
  1442. 55:52when you have the critical card at each
  1443. 55:54tower
  1444. 55:56then you can determine the mean time
  1445. 55:58between failure
  1446. 56:01if you've watched the switching
  1447. 56:03insulation combination video
  1448. 56:05you've seen that we have two methods
  1449. 56:07deterministic and statistical for
  1450. 56:09non-self restoring insulation and
  1451. 56:12self-resting insulation
  1452. 56:14but like i said at the beginning of this
  1453. 56:16one here there is no need
  1454. 56:17um for this for lightning you can
  1455. 56:21you can use the deterministic method for
  1456. 56:23all type of insulator
  1457. 56:25because of the low dispersion of
  1458. 56:28the insulation correct the the waste and
  1459. 56:32probably the western voltage probability
  1460. 56:34okay so once
  1461. 56:36you have uh your critical current
  1462. 56:40you use here and a standard
  1463. 56:43probability function to determine the
  1464. 56:46probability to have
  1465. 56:48such an intensity such a
  1466. 56:52current constituent like me for example
  1467. 56:55you remember i did here my simulation
  1468. 56:58for the first hour and i found 75
  1469. 57:02kilohertz for the critical current
  1470. 57:06then i use this equation here
  1471. 57:11it will tell me the probability to have
  1472. 57:13such a lightning
  1473. 57:14and i will assume it's the same
  1474. 57:16probability
  1475. 57:18for the entire distance covered by this
  1476. 57:20tower so basically for half of
  1477. 57:22from half of this line to half of this
  1478. 57:24line i will assume this critical
  1479. 57:26current just so i don't do so many
  1480. 57:28simulations you have to simplify the
  1481. 57:29problem
  1482. 57:30and then you have this probability for
  1483. 57:33all this section of line
  1484. 57:35then you will do the same thing here and
  1485. 57:36you will have the same probability there
  1486. 57:43okay so once you have the probability
  1487. 57:46like that for each section
  1488. 57:48you can calculate the annual number of
  1489. 57:52straw of
  1490. 57:53strokes okay so for that
  1491. 57:56the way you will calculate that is the
  1492. 57:58ground density
  1493. 57:59multiplied by multiplied by twice
  1494. 58:03r a or a i will
  1495. 58:06go back here to show you what it is
  1496. 58:17go back where i was
  1497. 58:22and b is the distance between each
  1498. 58:24conductor
  1499. 58:30okay so when you have so you have the
  1500. 58:32annual number of strokes
  1501. 58:34you multiply that by the probability you
  1502. 58:37get
  1503. 58:38for each section of line and
  1504. 58:42k t it's an extra coefficient to add
  1505. 58:46in the insulation coordination procedure
  1506. 58:49which depends on the tower resistance
  1507. 58:54okay so you will adjust this t 60 or 100
  1508. 58:57percent for if it's a high resistance
  1509. 58:58tower you use 100
  1510. 59:00else to 60 of chance and so that's how
  1511. 59:03you calculate now
  1512. 59:04the number of backlash over for each
  1513. 59:07section of line
  1514. 59:08and you do that for expand
  1515. 59:11until the critical distance and you can
  1516. 59:14add up
  1517. 59:14all these numbers to finally get
  1518. 59:18uh the number of um the
  1519. 59:22the annual number of backslash over
  1520. 59:26okay so it's um it seems like uh it's
  1521. 59:28difficult but it's actually not so
  1522. 59:30difficult
  1523. 59:32okay so if you need more readings
  1524. 59:36you have here some references i
  1525. 59:38recommend you to take a look at

About this transcript

This page contains the full transcript of Insulation coordination – Lightning transient overvoltages by EMTP, generated from the public captions YouTube serves with the video. The transcript has 8,518 words across 1,525 segments, with the original timestamps preserved so you can click any line to jump to that moment in the embedded player.

What you can do with it

Use the transcript to take notes, quote the speaker, build a study guide, generate a summary with ChatGPT or Claude via the YouTube Summary tool, or export it as a timed subtitle file with YouTube to SRT. You can also re-open it in the transcriber to choose a caption track available on the video.

Free YouTube transcript tool

YouTube2Text is a free YouTube transcript generator — no signup, no daily limit. Paste any YouTube link and get the full transcript instantly, with timestamps, click-to-jump, caption language selection, AI prompts for ChatGPT, Claude, and Gemini, and exports to TXT, SRT, VTT, or Markdown.